i-COMM™ CONTROLLER

Pub. No. RHSPI388 JANUARY 2006    

7

i-COMM DIGITAL CONTROLLER INSTRUCTIONS

Valid Values for Output Settings

Value

Function

0

On when door closed (Interlock Out)

1

On when door Not Closed

On during preannounce to close

3

On when door full open

4

On when door not full open

5

On when door faulted

6

On when door not faulted

7

On when activation command

8

On during run Open

9

On during run Close

10

On during run (Open or Close)

11

On when door on limit  (open or close)

12

On when I-Zone alarm

13

On when door open for 30 seconds

14

On when door open for 60 seconds

15

On when door open for 120 seconds

16

On during sequential activation

17

On when not running open

18

On when not running close

19

On when not running (open or close)

20

Output Disabled

Default Value for Output (Factory Configuration)

Model:

YK2

YK3

YDC0

YDC1 YDC2 YDC3

Protecdor/CL

n/a

0

2

20

20

20

Protecdor/CL PRO

n/a

0

2

20

20

n/a

Protecdor XL

n/a

0

2

20

20

20

Protecdor XL PRO

n/a

0

2

20

20

20

Trakline

20

0

2

20

20

20

Iso-Tek

n/a

0

2

20

20

20

Barrier Glider

n/a

0

2

20

20

n/a

Barrier Fold

n/a

0

2

20

20

20

n/a = Not available for change

DETAILED MENU LISTING:

"Output Definition" 

Read-Write

Use to change functions of outputs where allowed. YK2, YK3, YDC0, 

(see chart)

(Note:  Outputs which are not changeable will display "Not Adjustable")
YDC1, YDC2, YDC3

Summary of Contents for i-COMM

Page 1: ...i COMM CONTROLLER Pub No RHSPI388 JANUARY 2006 1 i COMM DIGITAL CONTROLLER INSTRUCTIONS...

Page 2: ...5 Unplug the J5 induction loop harness if applicable 6 Remove wires from the input and output terminals 7 Remove the board by cutting the white plastic supports and remove supports from bracket 8 Ins...

Page 3: ...ROLLER INSTRUCTIONS Input Terminals LCD Display Output Terminals Display Contrast Potentiometer Lighter Darker Down Key Up Key Enter Key J1 Programming Port Green Input Terminal LED s Power LED Red Ou...

Page 4: ...Door has detected obstruction and reversed 3 times Inspect Reset Unknown Unknown fault Service Required System Clock read System clock failed Service Required Unknown State State unknown Service Requi...

Page 5: ...4VAC INPUT 24VAC COMMON N OPEN CLOSE COM INVERTER OUT 2 K1 INVERTER OUT 1 K0 LOOP INPUT 2 LOOP INPUT 1 DC POWER OUT DC COMMON OUT DC POWER OUT LOOP INPUT X13 BARRIER GLIDER 7100 OPEN L S CLOSE L S SPA...

Page 6: ...Read Write Displays and sets Preannounce to close timer This time plus the Close Timer will be the amount of time the door will stay open Valid Range 0 255 seconds All models Display Serial Read Only...

Page 7: ...for 60 seconds 15 On when door open for 120 seconds 16 On during sequential activation 17 On when not running open 18 On when not running close 19 On when not running open or close 20 Output Disabled...

Page 8: ...ult History Read Only Displays Last five faults as codes Use arrows to provide a detailed description of each fault code displayed Kick Close Time Read Write Sets Kick Time on Barrier Fold door Valid...

Reviews: