CURRENT THD
TRIGGER VALUE
( 1 - 99 % )
RELAY ACTIVATION
CURRENT THD : When current THD is more
than set limit then PF controller will operate relay
Press ENTER key to enter into current THD sub setup.
Pressing UP or DOWN key will scroll through submenus.
TRIGGER VALUE : Value is settable from 1 to 99%.
Press ENTER key to edit trigger value.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.
RELAY ACTIVATION : PFC allows to activate / deactivate
assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
Note :
- 1. If fault occurs APFC will Switch off all banks
including fixed banks one after the other with a delay of
1second
2.Relay will reset at set current THD minus 5%.
Reset point is factory set, not editable.
41