SYS NOM VOLTAGE
SYSTEM NOMINAL VOLTAGE :This is the system rated
voltage with respect to which the fault limits
are defined. Value is settable from 50 to 550 VAC.
Press ENTER key to edit system nominal value.
Pressing UP or DOWN key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed values.
CAPACITOR KVAr
CAPACITOR KVAr: Assigns Capacitor KVAr for outputs.
following 3 option possible
1.AUTO DETECTED: KVAr detected by auto detection
function
2.DIRECT Kvar: Individual capacitor KVAr can be
programmed independent of other capacitor banks
3.CONTROL SERIES. Predefined sequence is Ratio of
capacitor KVAr with reference to first step
Press ENTER key to edit Capacitor KVAr selection option
Pressing UP or DOWN key will scroll available options
Then pressing ENTER key confirms the option
PHASE CORR. ANGLE
PHASE CORRECTION ANGLE: Selects phase correction
angle for inputs applied following two options possible
1. AUTO DETECTED: phase correction angle as
detected by auto detection function
2. USER SETTINGS: use correction angle as set in
system setup menu of input current and voltage
Press ENTER key to edit phase correction angle
Pressing UP or DOWN key will scroll available options
Then pressing ENTER key confirms the option