10b. Once measurement is complete and any
capacitance has been discharged, the
instrument shows:
The value of the measured insulation
resistance
The value of the actually generated
voltage V1
The value of the time relevant to
parameter T1
If the measured resistance value is not
between the (MIN - MAX) limits
previously set, the instrument shows
NOT OK, the alarm bell and gives a long
acoustic signal (see § (§ 4.10.1, §
4.10.2, § 4.10.3)
11.
Once measurement is complete, it is also possible to display the leakage current, the
capacitance the number N of cycles in which the set ramp was repeated, which cyclically
show when pressing the arrow keys
CAUTION
If the measured resistance value < 5.0M
, the screen displaying the capacitance
shows three hyphens “---“, to indicate that it was impossible to measure the
capacitance, and the CAUTION triangle
If, when scrolling the results obtained, the capacitance value is > 1nF, it is
recommended to repeat the measurement by activating the SMOOTH function
(see § 4.11)
12.
Measures can be saved by pressing the
SAVE
key twice (see § 5.1)