4.1  EMC Installation Requirements

This product has been designed to meet the certification of the EU directives when 
installed to a good code of practice for EMC in industrial environments, e.g.

1. Screened output and low signal input leads or have provision for fitting RF 
    suppression components, such as ferrite absorbers, line filters etc., in the event 
    that RF fields cause problems.

NOTE: 

It is good practice to install sensitive electronic instruments that are 

            performing critical functions, in EMC enclosures that protect against electrical 
            interference which could cause a disturbance in function.

2. Avoid routing leads alongside cables and products that are, or could be, a source 
    of interference.

3. To protect the product against permanent damage, surge transients must be 
    limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at 
    the source. The unit has been designed to automatically recover in the event of a 
    high level of transients.  In extreme circumstances it may be necessary to 
    temporarily disconnect the auxiliary supply for a period of greater than 5 seconds 
    to restore correct operation.

4. ESD precautions must be taken at all times when handling this product.     

18

Summary of Contents for Eine+

Page 1: ...RISH Eine Operating Manual 2 60 006 00 00510_Rev_E 3 2018 1 ...

Page 2: ... 2 3 Display start value 3 1 2 4 Bent function selection 3 1 2 5 Input bent value 3 1 2 6 Display bent value 3 1 3 Power Factor Meter 3 1 3 1 Input start value 3 1 3 2 PF end value 3 1 3 3 PF start value 4 1 EMC Installation Requirements 4 2 Case Dimensions and Panel Cut out 4 3 Wiring 4 4 Auxiliary Supply 4 5 Fusing 4 6 Earth Ground Connections 5 Connection Diagrams Specifications 6 DC Voltmeter ...

Page 3: ... technology The parameters are displayed with Ultra high bright LED display with 14mm Digit height Programmable DPM can be configured and programmed on site for the following Input start and bent values Display start end and bent values The front panel has two push buttons through which the user can enter into programming mode and can configure the meter 1 Eine mV 2 Eine mA 3 Eine V 4 Eine A V A A...

Page 4: ...remental order by pressing the key and in decrementing order by pressing key Screen 1 Voltage Screen 3 Ambient Temperature F Screen 1 Current Screens of Eine mA mV Screen 2 Ambient Temperature C mV mV A flashing message of F will be shown at intervals of 1 5 sec Note All the screen shown in manual is for reference Screens are applicable for both models i e 48x96 96x96 5 ...

Page 5: ...ec 3 1 2 Eine Setup Parameter Screen tYPE Meter Type Sec 3 1 1 PF end value PF E Sec 3 1 3 2 PF S PF start value Sec 3 1 3 3 inP S Input start Sec 3 1 2 1 dSP E Display end value Sec 3 1 2 2 dSP S Display start value Sec 3 1 2 3 bEnt Bent function on off Sec 3 1 2 4 inP b Input bent value Sec 3 1 2 5 dSP b Display bent value Sec 3 1 2 6 A A OFF ON 6 ...

Page 6: ...he following options using the up key nor normal operation PF operate as Power Factor DPM Pressing the down key will accept the present type and advance to Input Start value selection section 3 1 2 1 Pressing the up key again will enter the meter type edit mode and user can scroll through the types available Pressing the down key advances to the meter type confirmation menu Meter Type Confirmation...

Page 7: ...the edit mode by pressing the key user can turn the symbol On or Off If symbol is On then Input Start value will be set as negative Pressing the key will set the symbol and editing of first digit will start By pressing the key user can scroll the value from 0 to 9 or it will get restricted by Input End value Pressing the key will set the first digit and advance the operation to next digit Similarl...

Page 8: ...set the symbol Next on pressing key editing of Decimal point will start With each press of the same key the Decimal point will shift towards right by one digit Pressing the key will set the decimal point position and advance to digit editing By pressing the key user can scroll the value from 0 to 9 Pressing the key will set the first digit and advance the operation to next digit Similarly user can...

Page 9: ... Selection menu section 3 1 2 4 After entering the edit mode by pressing the key user can turn the symbol On or Off If symbol is On then Display Start value will be set as negative else it will be positive Pressing the key will set the symbol and editing of first digit will start By pressing the key user can scroll the value from 0 to 9 Pressing the key will set the first digit and advance the ope...

Page 10: ...ent Value inP b This screen appears only when Bent Function has been enabled This screen allows the user to set the Input Bent value The Bent value can be set in between Input Start value 1 5 of Input End value and 98 5 of Input End value Initially inP b message is displayed on screen following which user can start editing Input Bent value by pressing the key Instead on pressing the key will confi...

Page 11: ...essing the key user can scroll the value from 0 to 9 or it will get restricted depending upon Display Start and End value Pressing the key will set the first digit and advance the operation to next digit Similarly user can edit the remaining three digits After all four digits have been set pressing the key will advance to the Display Bent value confirmation mode Pressing the key will re enter into...

Page 12: ... to 1 quadrants 1 2 Initially PF E message is displayed on screen following which user can start editing PF End value by pressing the key Instead on pressing the key will confirm the present value and advance to PF Start value selection section 3 1 3 3 Capacitive Inductive Capacitive Inductive PHASOR DIAGRAM Phasor Diagram 3 1 3 1 Input Start Value inP S Refer section 3 1 2 1 13 ...

Page 13: ...nd value confirmation mode Pressing the key will re enter into the End value edit mode Pressing the key will confirm the set value and advance to PF Start value selection section 3 1 3 3 NOTE The decimal point position will remain fixed after the first digit both in setup and in the measurement screen 3 1 3 3 PF Start Value PF S This screen allows the user to set the PF Start value which will corr...

Page 14: ...ressing the key will advance to the PF Start value confirmation mode Pressing the key will re enter into the Start value edit mode Pressing the key will confirm the set value and exit the Setup menu to return to measurement mode 3 2 Other Display Indications oL Indication Overload indication above 125 input Description When display count exceeds 9999 ve reading For 4 20mA range if meter setting is...

Page 15: ...temperature is 0 within the range 10 to 55 C Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight Easy Clip in mounting Swivel screw 4 Installation Mounting of EINE is featured with easy Clip in mounting Push the meter in panel slot size 92 x92 mm it will click fit into panel with the four integral retention clips on tw...

Page 16: ...stable ambient temperature and where the operating temperature is within the range 10 C to 55 C Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight Caution 1 In the interest of safety and functionality this product must be installed by a qualified engineer abiding by any local regulations 2 Voltages dangerous to human ...

Page 17: ...enclosures that protect against electrical interference which could cause a disturbance in function 2 Avoid routing leads alongside cables and products that are or could be a source of interference 3 To protect the product against permanent damage surge transients must be limited to 2kV pk It is good EMC practice to suppress differential surges to 2kV at the source The unit has been designed to au...

Page 18: ...nputs will accept up to 4mm 12 AWG or 2 2 5mm 12AWG Standard Note 1 It is recommended to use wire with lug for connection with meter 2 For disconnecting the device a switch or circuit breaker shall be included at the site and shall be within easy reach of the operator The specification are as below For Aux At least 1 5 times of applied Power supply For Measuring Input At least 1 5 times of applied...

Page 19: ... B A Aux Supply L N Aux Supply N L 0 500V 0 1000V 96x96 model 48x96 model 4 4 Auxiliary Supply Eine should ideally be powered from a dedicated supply 4 5 Fusing It is recommended that all voltage lines are fitted with 1 amp HRC fuse 4 6 Earth Ground Connections For safety reasons panels and accesoriess should be grounded in accordance 3 1 ...

Page 20: ...terval 5 times at 5 min interval Overload Indication oL If input is greater than 125 of nominal value Nominal Input Current Ranges Max continuous input current 120 of nominal value Voltage Drop 600 mV 10 0 10 mA 20 0 20 mA 4 20 mA 1 0 1 V 5 0 5 V Measuring Range Eine Current Input Current 300 uA Max continuous input voltage 120 of nominal value 0 500 V 0 1000 V 5 0 5 V 10 0 10 V Nominal Input Volt...

Page 21: ... m min Level 3 industrial low level Electromagnetic radiation environment 9999 9999 Display Range 0 05 C plus Temperature Coefficient 0 025 C Zero point drift Influence of Variations Reference conditions for Accuracy Reference temperature 0 0 23 C 2 C Auxiliary Supply Voltage Rated value 1 Auxiliary Supply Frequency Rated value 1 Accuracy Current mA A 0 5 of Display End value 1 digit Voltage mV V ...

Page 22: ... Material Screw type terminals Terminals IP54 For 48x96 model For 96 x 96mm Safety 2 III Pollution Degree Installation Category High Voltage Test 2 2 kV AC 50 Hz for 1 minute Environmental conditions 0 10 to 55 C 0 25 to 70 C 0 90 Non condensing Minimum 3 minute 15g in 3 planes 10 55 Hz 0 15mm amplitude Operating temperature Storage temperature Relative humidity Warm up time Shock Vibration 23 ...

Page 23: ...for this product and in no case will Manufacturer be liable for any other to make electrical power installations and is intended to describe the correct method of installation for this product However Manufacturer has no control over the field condition which influence product installation Incidental indirect or consequential damages arising from the use or misuse of the products Bezel Size DIN 43...

Reviews: