44
| Linear installation guide 13563-H 08-19
This end of the flexible
air hose comes already
connected to the air
inlet.
Rubber cap placed on
the unused air intake
Air intake hose
connected to the
LSFKIT01
and
secured with a cable tie
Flue lock bracket
holding the
LSFKIT01
in place.
LSFKIT01
connected
into the Linear
combustion fan
exhaust.
Air hose connection
This step in the installation is critical. If the connections are not secured properly, products
of combustion could disperse into the room being heated.
The Linear comes with one end of the flexible air hose already connected to the Linear air inlet.
Attach the other end of the air intake hose to the connection on the flue, either the ASPDFK or the
LSFKIT01.
Connect the flue into the Linear combustion fan exhaust, and secure in place (two screws) with the
flue lock bracket (supplied in the plastic bag with the remote control).
Secure the air intake hose on the flue with the cable tie (supplied in the plastic bag with the remote
control), and ensure the rubber cap is in place on the unused air intake.
WARNING
Flue exhaust
connection
Small air inlet connection
Large air inlet
connection
ASPDFK
LSFKIT01
Air inlet hose
Flue exhaust
connection
(Rubber cap
MUST
remain in place)
Flue exhaust
locking bracket