| Linear installation guide 13563-H 08-19
side direct, side extended, side and back flueing
Flueing options
Creating a direct flue installation for wall less than 385 mm
1. Create the wall penetration. Allow for a continuous 2 ° fall from the heater connection point to
the wall terminal.
2. Slide the internal wall plate over the
terminal end of the ASPDFK pipe until it is
nested on the raised ring of the transition.
Pass the ASPDFK through the internal wall
penetration until the internal wall plate is
flush with the wall.
3. Create the wall terminal, refer p.43.
4. Move the Linear into place and connect
the heater flue pipe to the flue. This is
done with the flue slide stopper provided with the flue kit.
Creating a direct extended flue installation for a wall greater than 385 mm
1. Create the wall penetration. Allow for a continuous 2 ° fall from the heater connection point to
the wall terminal.
2.
Join the flue pipe to the ASPDFK, cutting is not required. The joints between ASPDFK and the
flue pipe MUST BE secured by screws through the outer pipes to prevent disconnection.
3. Follow steps 2-4 as outlined in the
previous section for creating a direct flue
installation.
Exterio
r wall
Exterior
wall
300 mm minimum of straight flue is required before any bends (achieved with the ASPDFK
and the flue transition extension—LSFEXTKIT01). This is required due to heat produced
from the initial section of the flue. The first 500 mm of flue requires a 25 mm clearance to
combustibles.
IMPORTANT