Rinnai REU V2632FFU Installation Instruction Download Page 4

Flueing Installation Instructions 

 

Rinnai Australia Pty Ltd     20/08/2003 

 

 

Page 4  of  10

  

 

1. Direct Flueing With Wall Terminal 

 

1. 

The Rinnai Infinity 'Direct Flueing components must be used for this purpose. These consist of a 90º-bend 
adaptor, wall terminal and one wall plate. An additional wall plate can be purchased as an optional extra for 
Internal Installation. 

2. 

Dimensions of the REU-V2632FFU/REU-V2632FFUC water heaters for 'direct' flueing are as shown in 

(Fig.7)

Ensure there is enough space to install the Infinity, flue assembly and pipe work. Also ensure that positioning 
of the flue terminal complies with the requirements of AS5601/AG601 

Clause 5.13.6.2

 / 

Fig.5.3 page 10.

 

 
Warning:

 The flue products can reach temperatures up to 200°C. The flue terminal is to terminate in a 

location, not to cause a nuisance. (AS5601/AG601/2002 clause 5.13.3.3). 
 

Installation 

 

1. 

Using the dimensions provided in 

(Fig.7)

 mark the top Water Heater location hole situated in the centre of the 

top-mounting bracket and the centre point for the flue terminal hole. 

2. 

Install the REU V2632 FFU water heater as per the installation instructions located in the pocket on the back 
of the front heater cover. 

3. 

When installing the 90º Bend Adaptor directly backwards from the appliance it is necessary to extend the 
mounting brackets of the water heater to the 50mm mark to allow for the radius of the bend. Loosen the 
heater-mounting bracket securing screws and adjust the heater away from the wall as far as possible. 

4. 

Drill a 135mm hole for the flue (Cover the flue spigot to avoid debris entering the appliance flue connection). 
NOTE: If the hole is drilled accurately the 90º adaptor bend will cover the hole and an internal wall plate will 
not be necessary. Otherwise an extra wall plate can be purchased. (Rinnai Part No. FFWPLATE). 

5. 

Measure the length of the horizontal terminal and cut to length allowing for the outer section of the flue to 
extend 10mm through the wall. (See the section cutting flue components 

(Fig.9)

6. 

From outside the building, fit the external wall plate to the flue terminal and place through the hole in the wall 

(Fig. 2). 

Connect the terminal onto the 90º adaptor bend. Ensure the wall terminal pushes 'fully home' into the 

adaptor. The arrow on the side of the bend will face the in the direction of discharge. 

7. 

To prevent rain water from entering the flue terminal ensure the required 2

o

 fall to outside is achieved 

(Fig. 2)

8. 

On the outer wall, secure the decorative wall plate. Ensure the 2º fall to the flue terminal is achieved. 

9. 

Seal the flue around the wall plate using silicon sealant.  

   

2. Horizontal Extension Flueing With Wall Terminal 

 
1. 

This option 

(Fig.2)

 can be used when the water heater is mounted against an internal wall and flueing needs to 

extend horizontally to exit an external wall. The Rinnai Infinity 'Direct Flueing components' must be used for this 
purpose, together with extension pieces & bends as required. 

Total flue length can be up to 9 metres long & 

a maximum of 3 bends can be used.

  

2. 

Dimensions of water heater with 90° bend adaptor connected are as shown in 

(Fig. 2 & 7)

 When the flue tracks 

horizontally, it should be installed to have a 2° fall towards the wall terminal to prevent condensation running 
back into the water heater as shown. Ensure there is enough space to install the Infinity, flue assembly and 
plumbing pipe work. Ensure that positioning of the flue terminal complies with the requirements of 
AS5601/AG601 

Clause 5.13.6.2

 / 

Fig.5.3 page 10.

 

 

Warning:

 The flue products can reach temperatures up to 200°C. The flue terminal is to terminate in a 

location, not to cause a nuisance. (AS5601/AG601 clause 5.13.3.3). 

 

Installation  

 

1. 

Using the dimensions provided in

 (Fig. 7)

, Install the REU-V2632FFU/REU-V2632FFUC water heater as per 

the installation instructions located in the pocket on the back of the front heater cover.  

Summary of Contents for REU V2632FFU

Page 1: ...ly installed Water Heater Models REU V2632FFU REU V2632FFUC UP UP UP This Flue shall be installed in accordance with Manufacturer s Installation Instructions Local Gas Fitting Regulations Municipal Bu...

Page 2: ...el single skin or stainless steel coaxial flue If in doubt contact the Rinnai Australia Technical Advice Helpline 1300 366 388 2 Before commencing installation please read the Installation Instruction...

Page 3: ...rrs and file a slight bevel on the outer edge to reduce any damage to the seal when inserting into the connecting fitting See the section Cutting the Flue Components Fig 9 127mm Hole FFWALLTERM UP FFB...

Page 4: ...length of the horizontal terminal and cut to length allowing for the outer section of the flue to extend 10mm through the wall See the section cutting flue components Fig 9 6 From outside the building...

Page 5: ...e length can be up to 9 metres long and a maximum of 3 bends can be used 2 All vertical installations start with the vertical adaptor This MUST be connected with the larger end Black outer seal facing...

Page 6: ...the requirements of AS5601 AG601 Clause 5 13 6 2 Fig 5 3 5 If the total length of the flue exceeds 1 5 meters a condensate trap MUST be installed either vertically or horizontally adjacent to the heat...

Page 7: ...ing the dimensions shown on page 9 calculate the required number and combination of extension pieces and bends to be connected between the Infinity unit and terminal cut the appropriate components to...

Page 8: ...m the condensate trap connection point to the point of discharge or tundish outside the building There must be no tap valve or any other restrictions in the condensate drain and the tundish MUST NOT b...

Page 9: ...0 Tickness 1mm Tickness 2mm 25 25 5 85 163 136 UP 116 136 170 FFU Flue Part Numbers DESCRIPTION CODE NUMBER BAR CODE NUMBER Vertical Adaptor FFADAPT 9314109107692 Elbow 90 Degrees Bend Adaptor FFBEND9...

Page 10: ...any other opening into a building with the exception of sub floor ventilation Space heaters up to 50 MJ h input 150 Other appliances up to 50 MJ h input 500 Appliances over 50 MJ h input and up to 15...