Flueing Installation Instructions for  

Internally installed Water Heater 

Models REU V2632FFU / REU V2632FFUC 

 

 

            

UP

UP

UP

 

 
 

This Flue shall be installed in accordance with: - 

Manufacturer’s Installation Instructions 
Local Gas Fitting Regulations 
Municipal Building Codes 
AGA Installation Code for Gas Burning Equipment 
Any other relevant Statutory Regulation 
This appliance and flue system must be installed,  
serviced and removed by an Authorised Person. 

Summary of Contents for REU V2632FFU

Page 1: ...ly installed Water Heater Models REU V2632FFU REU V2632FFUC UP UP UP This Flue shall be installed in accordance with Manufacturer s Installation Instructions Local Gas Fitting Regulations Municipal Bu...

Page 2: ...el single skin or stainless steel coaxial flue If in doubt contact the Rinnai Australia Technical Advice Helpline 1300 366 388 2 Before commencing installation please read the Installation Instruction...

Page 3: ...rrs and file a slight bevel on the outer edge to reduce any damage to the seal when inserting into the connecting fitting See the section Cutting the Flue Components Fig 9 127mm Hole FFWALLTERM UP FFB...

Page 4: ...length of the horizontal terminal and cut to length allowing for the outer section of the flue to extend 10mm through the wall See the section cutting flue components Fig 9 6 From outside the building...

Page 5: ...e length can be up to 9 metres long and a maximum of 3 bends can be used 2 All vertical installations start with the vertical adaptor This MUST be connected with the larger end Black outer seal facing...

Page 6: ...the requirements of AS5601 AG601 Clause 5 13 6 2 Fig 5 3 5 If the total length of the flue exceeds 1 5 meters a condensate trap MUST be installed either vertically or horizontally adjacent to the heat...

Page 7: ...ing the dimensions shown on page 9 calculate the required number and combination of extension pieces and bends to be connected between the Infinity unit and terminal cut the appropriate components to...

Page 8: ...m the condensate trap connection point to the point of discharge or tundish outside the building There must be no tap valve or any other restrictions in the condensate drain and the tundish MUST NOT b...

Page 9: ...0 Tickness 1mm Tickness 2mm 25 25 5 85 163 136 UP 116 136 170 FFU Flue Part Numbers DESCRIPTION CODE NUMBER BAR CODE NUMBER Vertical Adaptor FFADAPT 9314109107692 Elbow 90 Degrees Bend Adaptor FFBEND9...

Page 10: ...any other opening into a building with the exception of sub floor ventilation Space heaters up to 50 MJ h input 150 Other appliances up to 50 MJ h input 500 Appliances over 50 MJ h input and up to 15...