Gas supply and connection
Gas pipe sizing must consider the gas input to this appliance as well as all other gas appliances in the
premises. The gas meter and regulator must be specified for the total gas rate. An approved sizing
chart such as the one in AS/NZS 5601.1 should be used. The gas supply termination is inside the
heater and enters through the rear of the appliance.
Gas supply location
1.
Mark off the location for the vertical centreline of the
heater enclosure.
2.
To the right of the vertical centreline, mark off the
vertical and horizontal locations for the gas supply
penetration.
Gas supply location
310 mm
35 mm
WA
LL
Min
im
um
cle
ara
nc
e7
5m
m
Back of heater
230 mm
Supplied gas connection
The length of the gas supply
termination is measured from the
front of the enclosure.
Installer to terminate to suit and
fit supplied gas connection. Leak
test joint between the flexible gas
connection and termination.
Gas connection
Firmly grasp the stainless steel flexi pipe and
bend to line up with the gas control valve inlet,
then attach the pipe to the gas control valve and
tighten.
The use of a rubber hose for any gas connection to a fixed appliance is NOT
authorised by the manufacturer
IMPORTANT