Check the installation for the presence of air.
If there is a secondary pump installed and it
is not hydraulically separated, it could cause
a loss of pressure difference.
Check to ensure the pump is functioning and/or water
pressure sensor is working properly.
Ensure water pressure sensor is not clogged or defective.
Inspect water filter for debris.
Check pump for proper operation and flow rates.
Check for proper wiring of pump.
Check for use of balancing valves.
AIR: if boiler, inner boiler piping, or Low Loss
Header has a large air bubble in it the
pressure sensor will not see the pressure
spike that the pump generates when it starts.
The pressure spike is what tells the MCBA that
the pump has started.
The air bubble will absorb that spike. Bleed all
air from the system.
If an additional expansion tank is placed in the
system alongside an E-boiler that tank can
absorb the pump pressure spike as well. You
may need to isolate that tank to see if this
corrects the issue with BL 85.
An expansion that is not charged properly can
cause the pump’s pressure spike not to be
seen by the sensor causing a BL85.
Expansion tank pressure should be air charged
to match whatever water fill pressure that is
chosen for the closed loop. (Always above
14.5 psi)
Expansion tanks must be air charged only
when there is no water pressure on the wet
side of the diaphragm or the tank is removed
from the system. Once charged to the correct
air pressure it may be placed into the system
and the water fill pressure now may be set to
match the new tank pressure.
Summary of Contents for Q series
Page 4: ...4 008082013GW ...
Page 5: ...5 008082013GW Parts of the Boiler ...
Page 15: ...15 008082013GW Flue sensor or thermostat contact open ...
Page 27: ...27 008082013GW ...
Page 34: ...34 008082013GW Replace MCBA board main board ...
Page 39: ...39 008082013GW T1 Sensor Contact for supply sensor T1 open indicated by infinite ohm reading ...
Page 41: ...41 008082013GW ...
Page 42: ...42 008082013GW ...
Page 43: ...43 008082013GW Electrical short circuit possible water damage to MCBA main board ...
Page 47: ...47 008082013GW E 115 Replace MCBA board ...
Page 49: ...49 008082013GW Additional Troubleshooting Instructions ...
Page 50: ...50 008082013GW ...
Page 51: ...51 008082013GW Checking the O2 Setting ...
Page 55: ...55 008082013GW ...
Page 57: ...57 008082013GW Altering adjustments ...
Page 59: ...59 008082013GW ...
Page 60: ...60 008082013GW Activating factory settings Green button function ...
Page 61: ...61 008082013GW Isolating the boiler ...
Page 62: ...62 008082013GW Reset service interval counter ...