008082013GW
T5 sensor is registering too high of a
temperature. This error can only occur if
the optional T5 sensor is was purchased
and installed on the boiler.
This is the location of the T5 sensor if installed.
If the red tab is in place this sensor was never
installed, which means the circuit has
somehow been jumped out. Contact Rinnai
tech support for assist if you get the bL80
without the T5 sensor being installed.
Inspect vent system and all air passages
ways for blockage
212˚F is the default temperature setting for
parameter 84. Verify to see if the temperature
setting for this parameter is set higher than
the default. If so, inspect vent system for
blockage.
Summary of Contents for Q series
Page 4: ...4 008082013GW ...
Page 5: ...5 008082013GW Parts of the Boiler ...
Page 15: ...15 008082013GW Flue sensor or thermostat contact open ...
Page 27: ...27 008082013GW ...
Page 34: ...34 008082013GW Replace MCBA board main board ...
Page 39: ...39 008082013GW T1 Sensor Contact for supply sensor T1 open indicated by infinite ohm reading ...
Page 41: ...41 008082013GW ...
Page 42: ...42 008082013GW ...
Page 43: ...43 008082013GW Electrical short circuit possible water damage to MCBA main board ...
Page 47: ...47 008082013GW E 115 Replace MCBA board ...
Page 49: ...49 008082013GW Additional Troubleshooting Instructions ...
Page 50: ...50 008082013GW ...
Page 51: ...51 008082013GW Checking the O2 Setting ...
Page 55: ...55 008082013GW ...
Page 57: ...57 008082013GW Altering adjustments ...
Page 59: ...59 008082013GW ...
Page 60: ...60 008082013GW Activating factory settings Green button function ...
Page 61: ...61 008082013GW Isolating the boiler ...
Page 62: ...62 008082013GW Reset service interval counter ...