VERTICAL FLUE

The  Vertical  Flue  option  (Fig.  12)  is  used  for  flueing 

vertically through the roof and FFPPROOFCOWL and 

FFPPPIPE1000 

MUST

  be  used  for  this  purpose. 

Components  included  with  FFPPROOFCOWL  are: 

terminal  pipe,  2x  UV  protectors  and  1x  pipe  clip. 

Components  included  with  FFPPPIPE1000  are:  flue 

pipe, 1x pipe clip.

Installation Method

IMPORTANT

Refer to "Flue Length, Bends & Appliance 

Settings"  on  page  6  for  flue  run  length 

limitations.
Ensure  there  is  enough  space  to  install 

the water heater, flue assembly and pipe 

work.  Also  ensure  that  the  positioning 

of  the  flue  terminal  complies  with  the 

requirements  of  AS/NZS  5601  AS/NZS 

5601 (see page 12).
Refer  to  "Appliance  Spigot  Dimensions 

&  Centres"  on  page  5  when  creating 

access holes through floors and ceilings 

for flue pipe components.

1.  Mount the water heater in an appropriate location. 
2.  Set plumb bob from the centre of the heater flue 

outlet to ceiling marking position. Cut 140mm hole 

in plasterboard (or a suitable 'oval' for pitched roof 

applications).  Repeat  this  step  for  underside  of 

roofing.

3.  Install, the UV adaptor and the UV protectors into 

the  underside  of  the  flue  shroud  (trimming  to  fit 

where necessary), refer to "UV Roof Protectors" 

on page 6.

4.  Calculate  the  required  number  and  combination 

of  FFPPPIPE1000  lengths  and  cut  to  size  as 

required, see Fig.1, in section "Cutting The Flue 

Components" on page 5.

5.  Install decktite roof seal (Not supplied).
6.  Ensure the flue is fully supported independently 

of  the  appliance,  by  the  use  of  suitable  clips  or 

brackets,  in  accordance  with  AS/NZS  5601. 

Appropriate  standoff  brackets  are  supplied  with 

each  FFPPROOFCOWL  and  FFPPPIPE1000 

component.

7.  Ensure that the appliance can be removed without 

causing movement or displacement of the flue, in 

accordance with AS/NZS 5601.

8.  All PVC joints must be secured with the three (3) 

self tapping screws supplied with the component 

as shown in Fig. 13.

9.  Connect  condensate  drain  (go  to  "Condensate 

Drain" on page 10 for connection details).

Fig. 14

Fig. 12

FFPPPIPE1000

FFPPROOFCOWL

Includes: UV Adaptor (x1), UV Protector (x2) 

and Pipe Cilp / Wall bracket (x1)

FFPPPIPE1000

FFPPPIPE1000

Pipe Clip

x1 supplied with 

FFPPPIPE1000

FFPPPIPE1000

FFPPWALLKIT

FFPPBEND90

Pipe Clip

x1 supplied with 

FFPPPIPE1000

Pipe Clip

x1 supplied with 

FFPPPIPE1000

3˚ fall towards

water heater

Fig. 13

Pipe clip

x1 supplied with 

FFPPPIPE1000

FFPPROOFCOWL

Includes: UV Adaptor (x1), UV Protector (x2) 

and Pipe Cilp / Wall bracket (x1)

Ensure the UV 

protectors are 

installed outside 

of the decktite 

(not supplied).

FFPPBEND90

FFWSEAL

FFPPPIPE1000

Pipe clip

x1 supplied with 

FFPPPIPE1000

FFPPBEND45

FFWSEAL

Ensure the UV 

protectors are 

installed outside 

of the decktite 

(not supplied). 

Pipe Clip

x1 supplied with 

FFPPPIPE1000

FFPPPIPE1000

FFPPBEND90

x1 supplied with 

 FFPPWALLKIT

INSTALLATION METHODS

Summary of Contents for HD210i

Page 1: ...uit Rinnai Water Heater Models HD210i REU N3237FFC AK The flue components described within these instructions are ONLY suitable for use with the model s that is listed above They are NOT suitable nor...

Page 2: ...This appliance must be installed in accordance with Manufacturer s Installation Instructions Current AS NZS 3000 AS NZS 3500 AS NZS 5601 Plumbing Code of Australia PCA Local Regulations and Municipal...

Page 3: ...ns 6 UV Roof Protectors 6 Installation methods 7 FFPP Flueing Options 7 Direct Horizontal Flue 8 Extended Horizontal Flue 8 Vertical Flue 9 Combined Vertical Horizontal Flue 10 Condensate Drain 10 Imp...

Page 4: ...m to local regulations All dimensions referred to in these instructions are in millimetres unless otherwise specified These instructions ONLY apply to the Rinnai FFPP water heater coaxial flueing syst...

Page 5: ...ght The ONLY COMPONENTS that can be cut are as follows FFPPWALLKIT pipe not bend FFPPPIPE1000 FFPPROOFCOWL and UVROOF PROTECTORS Ensure all ends are cut square the use of a mitre box will ensure a cle...

Page 6: ...he relevant spacing and clearance dimensions for both vertical and horizontal multiple terminal installations Multiple Roof Terminal Installations The minimum horizontal separation between terminal ce...

Page 7: ...same as Direct Horizontal flueing with additional pipe required due to the longer horizontal distance Refer Extended Horizontal Flue on page 8 for details of this installation method C Vertical Flue I...

Page 8: ...as required Fit the internal wall seal to the terminal pipe 6 Connect the terminal pipe to starter bend ensuring components are pushed fully home Secure the PVC joints of bend to the terminal pipe wit...

Page 9: ...cut to size as required see Fig 1 in section Cutting The Flue Components on page 5 5 Install decktite roof seal Not supplied 6 Ensure the flue is fully supported independently of the appliance by the...

Page 10: ...pipes and fittings such as Unplasticised Polyvinyl Chloride UPVC or Polyethylene PE which is commonly used for irrigation piping Important Considerations For Condensate Drain Pipe NOTE The content of...

Page 11: ...ers may be joined together provided they conform with the requirements of the Installation Method on page 11 Common Stack Discharge Where individual water heaters are installed in a multi storey build...

Page 12: ...URE 6 2 in part LOCATION OF FLUE TERMINALS OF BALANCED FLUE ROOM SEALED FAN ASSISTED OR OUTDOOR APPLIANCES n j Horizontally from an openable window door non mechanical air inlet or any other opening i...

Page 13: ...FPPROOFCOWL Includes Vertical Terminal Pipe UV Adaptor x1 UV Protector x2 Pipe Clip Wall Bracket x1 Installation Instruction FFPPBEND90 Includes 90 Bend FFPPWALLKIT Includes Starter Bend FFPPBEND90 Ho...

Page 14: ...Rinnai 14 HW_CF_FFPP_FIM NOTES...

Page 15: ...Rinnai 15 HW_CF_FFPP_FIM NOTES...

Page 16: ...nformation visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai...

Reviews: