Rinnai
10
HW_CF_FFPP_FIM
COMBINED VERTICAL & HORIZONTAL FLUE
The Combined Vertical & Horizontal Flue option (Fig. 14, page 7) allows the water heater to be installed virtually
anywhere using a wall (FFPPWALLKIT) or roof (FFPPROOFCOWL) terminal. Extension pieces (FFPPPIPE1000,
FFPPBEND90 and FFPPBEND45) can be mounted horizontally or vertically as required.
Installation Method
IMPORTANT
Refer to "Flue Length, Bends & Appliance Settings" on page 6 for flue run length limitations.
All horizontal flue is to be installed with a 3° fall towards the water heater.
1. Using a combination of the installation procedures covered in the “EXTENDED HORIZONTAL FLUE” on
page 6 and "Vertical Flue" on page 9, determine and install the required components. Note that PVC
joints
MUST
be secured with the three (3) self tapping screws supplied with the component, refer to Fig. 13
on page 9.
CONDENSATE DRAIN
The Rinnai range of condensing water heaters generate condensate continuously at a rate of up to 5 litres per hour
as a by-product of highly efficient gas burner system. This condensate must be drained via a pipe to a suitable
point of discharge (Fig. 15). Because the condensate is a by-product of gas combustion it is mildly acidic.
For this reason copper tube and fittings
MUST NOT
be used as it will corrode. Instead, Rinnai recommend
plastic pipes and fittings such as Unplasticised Polyvinyl Chloride (UPVC) or Polyethylene (PE) which is commonly
used for irrigation piping.
Important Considerations For Condensate Drain Pipe
NOTE
The content of AS/NZS 3500 ‘Temperature / Pressure Relief and Expansion Control Valve Drain
Lines’ has been used as a guide in preparing these considerations.
Water heater drain outlet connection, R½” (15 mm) BSP male. Condensate drain outlet connection, 1/2”
(15mm) BSP male nylon (Note: the black plastic shipping cap
MUST
be removed from the condensate drain
outlet prior to water heater operation).
PE R½” BSP (15 mm) female to barbed irrigation system connector (13 – 19mm) or equivalent plastic fitting.
Drain pipe and fittings to match item
B
.
Continuous fall (of at least 2°) from water heater to discharge point. Lengths and bends in accordance with
‘Length & Changes Of Direction’ table below.
Suitable points of discharge are deemed to be drains, sewers or pits.
DO NOT
discharge onto electrical
connections, earth stakes, copper pipes, concrete paths or into a pond.
Length & Changes Of Direction
Maximum length and changes of direction greater than
45° for the drainage pipe to be in accordance with that
described in the Table 2.
2°
D
B
A
C
E
A
Remove cap from condensate drain outlet
NOTE
Condensate drain applies to
both internal and external
models, the external model
is shown in this illustration.
Fig. 15
A
B
C
D
E
Table 2.
Drainage lengths & changes of direction
Max length (Metres)
9
8
7
6
Max changes of direction >45°
3
4
5
6
INSTALLATION METHODS
Summary of Contents for HD210i
Page 14: ...Rinnai 14 HW_CF_FFPP_FIM NOTES...
Page 15: ...Rinnai 15 HW_CF_FFPP_FIM NOTES...