Installation & Servicing Instructions Rinnai E-Series
51
Parameter Mode
PARA
FACTORY
DESCRIPTION
RANGE
.
.
.
.
1
176°F
maximum supply temperature CH
68 - 176°F
2*
00
type of CH installation:
00 - 04
No pre-selection made.
Radiators, air heating, or convectors:
T max. supply 176°F K factor heating curve 2.3; gradient 10°F/min; gear differential 10°F
00
01 DO NOT USE
radiators with large surface areas or underfloor heating as additional heating:
T max. supply 158°F K factor heating curve 1.8; gradient 10°F/min; gear differential 10°F
02
under floor heating with radiators as additional heating:
T max. supply 140°F; K factor heating curve 1.5; gradient 8°F/min; gear differential 8°F
03
full under floor heating:
T max. supply 122°F; K factor heating curve 1.0; gradient 6°F/min; gear differential 6°F
04
3
max.
maximum power CH in kW (.. x3415 = .. BTU/hr)
min-max
4*
00
control principal with on / off thermostat:
100 % on / off thermostat
00
constant water circulation 22&23 closed contact day curve operation,
open contact night curve operation
01
5*
2.3
heating curve K-factor (see also heating curve graph)
0.2 - 3.5
6*
1.4
heating curve exponent (see also heating curve graph)
1.1 - 1.4
7*
14°F
heating curve climate zone (see also heating curve graph)
-4 - 32°F
10*
0°F
fine adjustment heating curve day temperature
-8 to 10°F
11*
0°F
fine adjustment heating curve night temperature
-8 to 10°F
14
10°F/min.
gradient speed °F/min.
0 - 28°F/min.
15*
00
Booster after night decrease*:
no
00
yes
01
23**
-4°F
Frost Temperature
-4 to 50°F
27
32°F
Minimum T-set CH
0 - 158°F
36
00
Type of three way valve and DHW fascility
VC 2010 / VC 8010
x0
Flow switch present and warming function plate heat exchanger ON
1x
Flow switch present and warming function plate heat exchanger OFF
2x
43
max.
Maximum power DHW in kW (.. x3415 = .. BTU/hr)
min-max
49
100%
Maximum pump capacity heating
100 %
73
0
Altitude and venting CFT. See chapter 6.7.7
0 - 100
89
00
Address
No function
-01
Bus thermostat
00
90
01
Display reading
°C and Bar
00
°F and PSI
01
.
.
.
.
Info Mode
INFO
FACTORY
DESCRIPTION
RANGE
.
.
.
.
1
°F
supply water temperature T1
4
°F
return water temperature T2
5
°F
DHW temperature T3
7
°F
outdoor temperature T4
8
°F
flue gas temperature T5 (optional sensor)
16
%
actual power in %
17
kW
actual power in kW (.. x3415 = .. BTU/hr)
18
kW
actual load in kW (.. x3415 = .. BTU/hr)
20
indication bus communication
21
GJ
consumption total in GJ (.. x 33 = .. m3)
22
GJ
consumption CH in GJ (.. x 33 = .. m3)
23
GJ
consumption DHW in GJ (.. x 33 = .. m3)
24
h
total number of burner run hours
25
h
number of burner run hours CH
26
h
number of burner run hours DHW
32
h
total number of hours counter
37
h
total number of run hours pump CH and DHW
46
h
within how many hours is service required
.
.
.
** this parameter should not be altered in systems utilizing zone valves without a low loss header plumbing kit or a differential pressure bypass valve.