Rinnai 11
HW Demand Duo Systems OIM
HD28I, HD210I (INTERNAL MODELS)
This appliance is designed for ‘Indoor’ installation only. It may be installed ‘Outdoors’ in an enclosure if the
requirements of AS/NZS 5601 Section 6 are satisfied. An enclosure is defined as a compartment, enclosed are of
partitioned off space primarily used for the installing of the appliance.
If installed in an enclosure either Internally or Externally, the location should be ventilated to allow gas to dissipate
and provision must be made for the safe disposal of any leaking water to a visible location.
This appliance must not be used as a domestic spa or swimming pool heater.
Two types of flue systems are available:
•
The Rinnai Commercial Common Flue System.
•
The Rinnai Co-Axial FFU flue system.
The use of non Rinnai flue components may result in a dangerous situation and violates regulations.
The appliance(s) must be located so that the flue terminal exits the building at a suitable point.
For detailed information refer to “FLUEING FOR INTERNAL MODELS” on page 13.
This appliance must be located so that the flue terminal exits the building at a suitable point.
If a horizontal (wall) terminal is used, the location must be in accordance with Section 6 and Figure 6.2 of AS/
NZS 5601. Figure 6.2 is reproduced under ‘HORIZONTAL FLUE TERMINAL CLEARANCES’ on page 12 of this
manual.
If a vertical (roof) terminal is used, the location must be in accordance with Section 6 of AS/NZS 5601 and the
‘FLUEING FOR INTERNAL MODELS’ on page 12.
HORIZONTAL OBSTRUCTIONS
AS/NZS 5601-2010 ‘Gas Installations’ stipulates a minimum horizontal clearance of 500mm between a building
structure and obstruction facing the terminal.
For Rinnai External continuous flow water heaters such a building structure must ‘obstruct’ the full front cover
height of the appliance, or extend vertically above and below the front cover.
There must be no partial obstructions to the front cover of the appliance or any other parts of the appliance casing.
This will avoid the appliance failing to operate under windy conditions.
500mm
INSTALLATION INSTRUCTIONS