Use only the materials listed in the Water Heater Manual and this guide for vent, combustion air intake pipe and 
fittings (See table 1). Failure to comply with this warning could result in severe personal injury, death or                        
substantial property damage.

 

 

     

WARNING

 

 
 
If used, a masonry chimney can 

ONLY

 be used as a 

PIPE CHASE 

for the exhaust and combustion air intake 

pipes.  The exhaust and air piping must be installed as instructed in this guide and applicable Water Heater              
Manual. The chimney must be used only for Rinnai Water Heater(s) vent chase. 

NO OTHER 

appliance or                 

fireplace can be connected to the chimney. Exhaust and air piping materials must comply with this instruction. 
The chimney must be fitted with a sealed access opening to facilitate interior inspection. The chimney chase (and 
liner, if installed) to be inspected annually for any degradation. Failure to comply could result in severe personal 
injury, death, or substantial property damage.  

     

WARNING

 

 

 

Combustion Air Intake - 

Install combustion air inlet piping for the condensing tankless water heaters as                    

described in the Water Heater Manual and this guide. The combustion air intake termination fitting must be               
installed with the clearances and geometry relative to the exhaust (vent) depicted in this document to ensure that 
flue products do not enter the combustion air intake. Ensure that the intake air will not contain any of the                       
contaminants as outlined in the “

Determine Installation Location

” section of this document. Contaminated              

intake air will damage the water heater, resulting in possible severe personal injury, death, or substantial property 
damage. 
 

Exhaust

 - Provide exhaust (vent) piping to Water Heater as specified in this guide and as required by all                     

applicable codes. The exhaust (vent) termination fitting must be installed with the clearances and geometry                 
relative to the combustion air  pipe as depicted in this document to ensure that flue products do not enter the 
combustion air intake 

 

     

WARNING

 

 
 
Tankless Water Heaters must be vented and furnished with intake air and exhaust vent using piping and                  
methods described in this guide and the appliance installation instructions. Each water heater must have its own 
intake and vent. DO NOT common vent with any other appliance using this method. Inspect finished vent and 
intake air piping thoroughly to ensure all are airtight and comply with the instructions provided and with all                     
requirements of applicable codes. Failure to provide a properly installed vent and air system will cause severe 
personal injury or death.

 

 

     

DANGER

 

 
 
Installations must comply with local requirements and with the National Fuel Gas Code, 

ANSI Z223.1/NFPA 54

 

for U.S. installations or CSA B149.1 for Canadian installations. 

DO NOT

 use cellular core PVC, CPVC, or Radel 

based pipe materials for the exhaust vent. Vents 

MUST

 be of solid core pipes ONLY.

 

 

     

WARNING

 

 
 
If the vent and/or combustion air intake piping configurations covered in the Water Heater Manual and this guide 
cannot be applied to a specific installation, contact Rinnai’s Application Engineer group for assistance. Other                         
configurations may be available.

 

 

     NOTICE

 

Summary of Contents for Circ-Logic RU80i

Page 1: ...TWIN PIPE PVC CPVC VENTING GUIDE FOR CONDENSING TANKLESS WATER HEATERS...

Page 2: ...Multiple Water Heaters 22 17 Vertical Termination of U Vent and Combustion Air Pipe on a Pitched Roof 22 18 Ubbink Concentric to Twin Pipe Adaptor 23 Tables 1 Vent and Air Piping Materials 5 2 Recomm...

Page 3: ...ERNATIVE TWIN PIPE PVC CPVC VENTING SYSTEM The newly certified vent system is comprised of a Concentric to Twin Pipe Adaptor adaptable to 3 and 4 inch sizes PVC CPVC pipes fittings and either the IPEX...

Page 4: ...ection of this document Contaminated intake air will damage the water heater resulting in possible severe personal injury death or substantial property damage Exhaust Provide exhaust vent piping to Wa...

Page 5: ...primer PVC ANSI ASTM D2564 CPVC ANSI ASTM F493 IPEX bird screens purchase separately Termination Vent Screens Polyethylene 3 Vent screen IPEX part 196051 4 Vent screen part 196052 Screens are frictio...

Page 6: ...ls Before installation consider where air has the ability to travel within the building to the water heater Where possible install the water heater in a sealed closet so that it is protected from the...

Page 7: ...snow level in your area Ref Description Canadian Installations US Installations A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door tha...

Page 8: ...at same level 0 30 m to an inside corner 0 30 m between terminals at same level 24 V 0 61 m to wall or parapet 12 V V 60 V V 1 52 m between terminals at different levels Figure 2 Required Clearances...

Page 9: ...A blank copy of the Vent Length Calculation Sheet is located at the end of this guide Ensure switch 1 in the bank of eight tan dip switches is in OFF position if vent length is greater than 21ft 6 4m...

Page 10: ...ed into the straight pipe lengths below 20 6 1 10 3 0 5 1 5 5 1 5 of 90 Elbows each 5 equivalent feet Max straight pipe vent length in feet meters 0 45 13 7 55 16 8 60 18 3 60 18 3 1 40 12 2 50 15 2 5...

Page 11: ...ach 5 equivalent feet Max straight pipe vent length in feet meters 0 21 6 4 31 9 4 36 11 0 36 11 0 1 16 4 9 26 7 9 31 9 4 31 9 4 2 11 3 4 21 6 4 26 7 9 26 7 9 3 6 1 8 16 4 9 21 6 4 21 6 4 4 11 3 4 16...

Page 12: ...stems ULC S636 Components of any certified system CANNOT be substituted with any other vent system s or unlisted pipes and or fittings All listed components primers and glues are part of the certified...

Page 13: ...or other type of reducing fittings is required to transition to 4 pipe STEP 5 Apply lubricant to the gasket surface and coupling with finger prior to component attachment refer to installation exampl...

Page 14: ...mbly Configuration The adaptor as supplied requires no additional parts to be used with standard 3 3rd party solid core PVC CPVC pipes refer to Figure 6 below for required parts for 3 PVC CPVC assembl...

Page 15: ...ng material contact PVC CPVC manufacturer for a complete list IPEX Concentric Vent Kit CVK Installation For installations with multiple terminations maintain appropriate clearances between terminals r...

Page 16: ...been determined cut a hole in the roof or wall large enough to accommodate the outer pipe The size of the hole can vary greatly depending on the roof pitch 2 As per the procedures outlined solvent ce...

Page 17: ...o IPEX PVC CPVC FGV Concentric Vent Kit ONLY for required spacing for all other termination types refer to Figures 12 thru 16 NOTE Reference General Clearance Requirements section of this guide for im...

Page 18: ...C Low Profile Termination Configuration VENTING INSTALLATION SEQUENCE 1 Install the water heater 2 Determine the termination method sidewall or vertical concentric or separate pipes etc 3 Determine pr...

Page 19: ...kit Be sure to follow guidelines for solvent cementing as described in the System 696 Installation Guide 3 Use the supplied screws and anchors to secure the base to the wall a drilled 3 16 hole 1 3 16...

Page 20: ...nd as shown in Figures 12 and 13 If the vent is terminated on a sidewall which is subject to high winds it is recommended to terminate the vent using a tee A tee provides the best protection against w...

Page 21: ...terminate using a tee or combination of elbows per figures 14 and 15 The termination must be installed 12 30 5 cm above roof or the highest anticipated snow level 3 The vent must terminate vertically...

Page 22: ...E DO NOT use lubricant between two PVC CPVC components Refer to cement manufacturer instruction for specific instructions and handling NOTICE Certified PVC CPVC Vent Termination Options continued Pitc...

Page 23: ...cable WARNING Improper installation of vent system and components or failure to follow all installation instructions can result in property damage or serious injury Lubricant can be applied on the sea...

Page 24: ...10 Approved PVC CPVC Termination Components OEM OEM orCert Product Description Diagram Equivalent Length Ft IPEX Purchased separately 196006 197009 3 Inch 196021 197021 4 Inch System 636 PVC CPVC FGV...

Page 25: ...mber of fittings Equivalent Vent Length Total Equivalent Length 1 90 elbow x 5 2 45 elbow x 2 5 3 IPEX Low Profile Termination x 5 4 IPEX 4 Concentric Termination x 20 5 IPEX 3 Concentric Termination...

Page 26: ...26 NOTES...

Page 27: ...27 NOTES...

Page 28: ...100000357 01 3 2014...

Reviews: