Adaptor Installation  

 

 

When installing the Ubbink adaptor with the twin 
pipe PVC/CPVC system

 

Install the system in according to Ubbink/Rolux, 
and Rinnai Installation Instructions. 

 

Use the 3”/5” Concentric to Twin pipe Adaptor 
with 3” or 4” diameter PVC/CPVC venting only. 

 

It is the responsibility of the installer to follow all 
national codes, standards and local ordinances, 
in addition to instructions laid out in this manual 
for vent/intake clearances and other safety                           
requirements. 

 

If venting conflicts arise between this guide and 
the respective OEM’s manual, the                           
manufactures’ installation instruction will take   
precedence providing they meet the intent of all 
national codes, standards and local ordinances 
having jurisdiction. Follow this guide                   
together with applicable codes, standards and/or                             
ordinances for installation of the intake/vent               
pipe(s) and all other applicable water heater                       
installation procedures.

 

PVC/CPVC Twin Pipe Adaptor Installation                   
Instructions: 

 

The vent size (diameter) and maximum vent lengths 
must be followed as detailed in the installation                 
Instructions supplied with the appliance and as stated 
in Tables 4-7 of this document. Thoroughly read and 
understand the venting section of the appliance                
manual before proceeding with the following steps    
outlined in this guide. 

 

NOTICE

 

For installation in Canada, field-supplied PVC/CPVC 
used for combustion venting must comply with CAN/
CGA B149.1 (latest edition) and be certified to Type 
BH Gas Venting Systems, ULC-S636.  

Components of any certified system CANNOT be 
substituted with any other vent system(s) or unlisted 
pipes and/or fittings.  All listed components, primers 
and glues are part of the certified vent system and 
therefore MUST be from a single manufacturer.  

STEP 1: 

                                                                                                                       

Carefully read and understand the venting section of 
the Installation Instructions supplied with the water 
heater prior to determining a suitable location for the 
water heater and vent termination. Locate water heater 
to have the straightest (shortest) practical vent length 
to outside. Measure the total venting distance required 
to reach the outside wall or roof. Determine the                  
diameter of venting components to be used based on                 
required vent length (refer to vent tables in tankless 
water heater manual or Tables 4-7 of this document). 

 

STEP 2:

 

                                                                                                                                                                  

Before installing the concentric to twin pipe adaptor, 
inspect each vent component for damage making sure 
the gaskets for each component are  undamaged. Do 
not attempt to install or repair damaged components. If 
a gasket is damaged, these are available through              
Rinnai and its distributors. Do not use gaskets from 
another manufacturer. 

 

STEP 3:

 

                                                                                                                                                   

Adaptor vent pipe MUST be securely fastened to           
structure, at the eccentric increaser or as close as     
possible thereafter (Figure 3). Straps to be field                  
supplied. Use straps, clamps or other fasteners that 
will not score or damage pipes and be acceptable by 
local codes.  

     

WARNING

 

Current codes prohibit the application of external          
insulation on plastic vent pipe together with the use 
of cellular core PVC, CPVC, and Radel as venting 
materials. 

Figure 3: Wall support for Eccentric Increaser 

Securing  Strap 

Eccentric 
Increaser 

Summary of Contents for Circ-Logic RU80i

Page 1: ...TWIN PIPE PVC CPVC VENTING GUIDE FOR CONDENSING TANKLESS WATER HEATERS...

Page 2: ...Multiple Water Heaters 22 17 Vertical Termination of U Vent and Combustion Air Pipe on a Pitched Roof 22 18 Ubbink Concentric to Twin Pipe Adaptor 23 Tables 1 Vent and Air Piping Materials 5 2 Recomm...

Page 3: ...ERNATIVE TWIN PIPE PVC CPVC VENTING SYSTEM The newly certified vent system is comprised of a Concentric to Twin Pipe Adaptor adaptable to 3 and 4 inch sizes PVC CPVC pipes fittings and either the IPEX...

Page 4: ...ection of this document Contaminated intake air will damage the water heater resulting in possible severe personal injury death or substantial property damage Exhaust Provide exhaust vent piping to Wa...

Page 5: ...primer PVC ANSI ASTM D2564 CPVC ANSI ASTM F493 IPEX bird screens purchase separately Termination Vent Screens Polyethylene 3 Vent screen IPEX part 196051 4 Vent screen part 196052 Screens are frictio...

Page 6: ...ls Before installation consider where air has the ability to travel within the building to the water heater Where possible install the water heater in a sealed closet so that it is protected from the...

Page 7: ...snow level in your area Ref Description Canadian Installations US Installations A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door tha...

Page 8: ...at same level 0 30 m to an inside corner 0 30 m between terminals at same level 24 V 0 61 m to wall or parapet 12 V V 60 V V 1 52 m between terminals at different levels Figure 2 Required Clearances...

Page 9: ...A blank copy of the Vent Length Calculation Sheet is located at the end of this guide Ensure switch 1 in the bank of eight tan dip switches is in OFF position if vent length is greater than 21ft 6 4m...

Page 10: ...ed into the straight pipe lengths below 20 6 1 10 3 0 5 1 5 5 1 5 of 90 Elbows each 5 equivalent feet Max straight pipe vent length in feet meters 0 45 13 7 55 16 8 60 18 3 60 18 3 1 40 12 2 50 15 2 5...

Page 11: ...ach 5 equivalent feet Max straight pipe vent length in feet meters 0 21 6 4 31 9 4 36 11 0 36 11 0 1 16 4 9 26 7 9 31 9 4 31 9 4 2 11 3 4 21 6 4 26 7 9 26 7 9 3 6 1 8 16 4 9 21 6 4 21 6 4 4 11 3 4 16...

Page 12: ...stems ULC S636 Components of any certified system CANNOT be substituted with any other vent system s or unlisted pipes and or fittings All listed components primers and glues are part of the certified...

Page 13: ...or other type of reducing fittings is required to transition to 4 pipe STEP 5 Apply lubricant to the gasket surface and coupling with finger prior to component attachment refer to installation exampl...

Page 14: ...mbly Configuration The adaptor as supplied requires no additional parts to be used with standard 3 3rd party solid core PVC CPVC pipes refer to Figure 6 below for required parts for 3 PVC CPVC assembl...

Page 15: ...ng material contact PVC CPVC manufacturer for a complete list IPEX Concentric Vent Kit CVK Installation For installations with multiple terminations maintain appropriate clearances between terminals r...

Page 16: ...been determined cut a hole in the roof or wall large enough to accommodate the outer pipe The size of the hole can vary greatly depending on the roof pitch 2 As per the procedures outlined solvent ce...

Page 17: ...o IPEX PVC CPVC FGV Concentric Vent Kit ONLY for required spacing for all other termination types refer to Figures 12 thru 16 NOTE Reference General Clearance Requirements section of this guide for im...

Page 18: ...C Low Profile Termination Configuration VENTING INSTALLATION SEQUENCE 1 Install the water heater 2 Determine the termination method sidewall or vertical concentric or separate pipes etc 3 Determine pr...

Page 19: ...kit Be sure to follow guidelines for solvent cementing as described in the System 696 Installation Guide 3 Use the supplied screws and anchors to secure the base to the wall a drilled 3 16 hole 1 3 16...

Page 20: ...nd as shown in Figures 12 and 13 If the vent is terminated on a sidewall which is subject to high winds it is recommended to terminate the vent using a tee A tee provides the best protection against w...

Page 21: ...terminate using a tee or combination of elbows per figures 14 and 15 The termination must be installed 12 30 5 cm above roof or the highest anticipated snow level 3 The vent must terminate vertically...

Page 22: ...E DO NOT use lubricant between two PVC CPVC components Refer to cement manufacturer instruction for specific instructions and handling NOTICE Certified PVC CPVC Vent Termination Options continued Pitc...

Page 23: ...cable WARNING Improper installation of vent system and components or failure to follow all installation instructions can result in property damage or serious injury Lubricant can be applied on the sea...

Page 24: ...10 Approved PVC CPVC Termination Components OEM OEM orCert Product Description Diagram Equivalent Length Ft IPEX Purchased separately 196006 197009 3 Inch 196021 197021 4 Inch System 636 PVC CPVC FGV...

Page 25: ...mber of fittings Equivalent Vent Length Total Equivalent Length 1 90 elbow x 5 2 45 elbow x 2 5 3 IPEX Low Profile Termination x 5 4 IPEX 4 Concentric Termination x 20 5 IPEX 3 Concentric Termination...

Page 26: ...26 NOTES...