6 Operations and Functions
6-3. External
output operation
- 29 -
6-3. External output operation
Signal Transmission System
Electric current transmission (non-isolated) 4
– 20 mA
Transmission Path
CVVS equivalent
Transmission Distance
CVVS equivalent 1.25 sq: Maximum 1.25 km
Connection Load Resistance
Below 300
Ω
1
Detection Mode
(No Alarm)
4 - 20 mA (concentration output)
2
Detection Mode
(Gas Alarm)
4 - 20 mA (concentration output)
3
Initial Clear
Depending on the setting of section 4.
2.5 mA setting: 2.5 mA
4 mA, HOLD, 4 - 20 mA setting: Equivalent to AIR
value (17.4 mA)
4
Maintenance Mode
2.5 mA setting: 2.5 mA
4 mA setting: Equivalent to AIR value (17.4 mA)
HOLD setting: The previous value retained
4 - 20 mA setting: 4 - 20 mA (concentration output)
5
Alarm Test
Output ON setting: 4 - 20 mA (concentration output)
Output OFF setting: The previous value retained
6
Fault Alarm
0.5 mA (Fixed)
7
INHIBIT
Depending on the setting of section 4.
2.5 mA setting: 2.5 mA
4 mA, HOLD, 4 - 20 mA setting: Equivalent to AIR
value (17.4 mA)
8
Power Off
0 mA
Example of Gas Concentration and External Output
0 - 25 vol% (Oxygen deficiency alarm specification)
Detection mode
Maintenance mode
Suppression value
Gas concentration
External output
17.4 mA
4 mA
20 mA
22 mA
Full scale
0
CAUTION
The 4 - 20 mA output is already adjusted. In case of over scale, an output will not exceed 22
mA.
Output during INHIBIT or initial clear is based on 4 - 20 mA output setting in the maintenance
mode.
In particular, when the detector is started or the specification is changed, be careful about 4-20
mA output setting. Understand how the detector functions, and take actions, if necessary, so
that the signal receiver side can prepare to avoid false alarms.
Summary of Contents for PT2-177
Page 1: ...PT2E 1771 Smart Transmitter Gas Detector Head SD 1OX Operating Manual PT2E 177 PT2 177 ...
Page 3: ......
Page 56: ......