4 How to Use
4-4. How to install
- 12 -
4-4. How to install
<Installation Dimensions and Maintenance Space>
The following installation requirements must be met to install the detector.
•
Attach the detector on the wall and others using four M6 screws.
NOTE
・
Hexagon socket head cap bolt with strength class "A2-70" are used.
When you lost or replace it, we recommend that you ask our local sales office nearest you.
・
Grease specified by RIKEN KEIKI : BARRIERTA JFE 552
(manufactured by NOK KLUBER)
If you can not prepare the specified grease, use one that meets the following requirements.
1. Material does not harden due to deterioration
2. Volatile solvent-free
3. Material does not cause corrosion at the surface
4. Silicon-free
5. Validation of suitability depends on the specifications of grease manufacturer
CAUTION
•
Do not install the detector in a place where maintenance of the detector cannot be performed
or where handling the detector involves dangers.
Regular maintenance of the detector must be performed.
Do not install the detector in a place where the machinery must be stopped when maintenance
is performed in its inside, where parts of the machinery must be removed to perform
maintenance, or where the detector cannot be removed because tubes or racks prevent access
to it. Do not install the detector in a place where maintenance involves dangers, for example,
near a high-voltage cable.
•
If the detector is to be fixed on a wall or the like, install it properly where can hold its weight.
Unit: mm
Wa
ll
4-
φ8
(for M6)
Summary of Contents for GD-1DOX-AS
Page 1: ...PT2E 2880 Fixed type Oxygen Detector Head GD 1DOX AS Operating Manual PT2 183...
Page 9: ......
Page 10: ......
Page 15: ......
Page 16: ......
Page 18: ......
Page 22: ......
Page 25: ......
Page 32: ......
Page 34: ...Manual Log Rev Amendment Issue data 0 First issue PT2 2880 1 31 2022...