INSTALLATION
Do not remove brick or mortar from the
fireplace to accommodate the stove.
The Integra Pellet Insert may be installed in a
variety of applications as follows:
a.
Listed, factory-built fireplaces
b.
Masonry fireplaces
c.
A newly constructed combustible framework
d.
Custom Hearth
©
stand-alone fireplaces
For masonry chimneys, a direct connection from
the exhaust to the first tile liner is required and the
flex pipe must terminate no less than 12” above
the air-tight seal.
For a combustible framework, the opening must
be a minimum of 25” high and 39” wide, with 2” of
clearance to the back of the stove. Floor
protection of
½“ USG
Micore and 24 guage sheet
steel or equivelent is required.
Shroud
Air-tight seal
Air-tight seal
Stove back
Tee
Clean-out Trap
Rain cap
Seal chimney
top with steel
plate only
Flexible or rigid
single-wall stain-
less steel pipe
Seal air-tight with
steel plate or with
Cera-Blanket
Flex pipe
Tee
VENTING INTO AN EXISTING CHIMNEY
When venting into an existing chimney, a full
reline is recommended.
Factory built and zero clearance fireplaces
require a listed stainless steel liner from the
exhaust to the termination of the chimney.
Floor protection must be a minimum of 3/8“ thick,
made of non-combustible material or equivelent,
extending a minimum of 6“ to the front and sides
of the door opening.
Before placing the stove in it’s final position, we
recommend the unit and all of it’s components be
fully assembled.
Summary of Contents for INTEGRA II
Page 1: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 1...
Page 32: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 32 CONTROL FLOW CHART...
Page 36: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 36...
Page 37: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 37...