![RIFT Actuators RIFT 200 Installation, Operation & Maintenance Instructions Manual Download Page 17](http://html1.mh-extra.com/html/rift-actuators/rift-200/rift-200_installation-operation-and-maintenance-instructions-manual_1460503017.webp)
17
SWITCHING RIFT® 200
‘
ON
’
(CONTINUED)
This is achieved on the RIFT® 200 by a single press & hold of the Auto/Manual Touch Pad until the Red LED
illuminates & flashes Red (8 O
’
clock position) and then touching either the open or close pads will send the
actuator towards that position whilst the touch pads are engaged or a double tap will complete the move
or move the actuator fully to the opposite position;
If external power is available and a remote command signal is being received (Auto), the actuator will
respect the remote command signal being applied and if not already in the commanded position, and
will move to it. If the actuator has been put into local control (Manual –
RED Flashing LED illuminated at
the 8 O'clock position) the local commands override the remote command signal and the actuator will
move to that selected position whilst the Open/Close Pads are pressed. The actuator will not accept
remote command signals until the actuator is put back into the remote command mode (Auto –
RED
FLASHING LED at the 8 O
’
clock position extinguished)
When the actuator is released from local control (Manual) the actuator will revert back to the last or
selected remote command position or Powered Position if no command given.
When mains power is unavailable, an internal trickle charged Li
-
Ion battery, supplied with the actuator,
provides internal power to allow use of the Touch Pads to open or close the actuator relative to the
Pad being pressed. On releasing the Pad, the actuator will stay put, on resumption of external power
the actuator will remain in local manual control and not move to the remote command position until
the Auto/Manual Touch Pad is pressed to release the actuator from this overriding control position
returning the actuator to normal remote control selected position.
If
it is
essential
that the actuator moves to a pre
-
determined position upon external power
failure,
you must
select and configure the RIFT® 200 actuator for
‘
FAILSAFE
’
functionality.
Auto/Manual Touch Pad selected (RED Flashing LED at the 8 O
’
clock position) for EMERGENCY HAND
OPERATION is as follows;
If the actuator is OPEN with an open signal applied, this will have no effect, but pressing the CLOSE Pad it
will start the actuator to rotate in a Clockwise (CW) direction and the RED LEDs will rotate in the direction
of movement, and when the CLOSE Pad is released, the actuator will stop in its current position and two
LED
’
s will be displayed to show the approximate position of the actuator. Press the OPEN Pad and the
actuator will move in a Counter Clockwise (CCW) direction and the LEDs will display Green. If the actuator
is CLOSED with a Close signal applied, this will have no effect, but pressing the OPEN Pad will start the
actuator to rotate in a CCW direction and the GREEN LEDs will rotate in the direction of movement, and
when the OPEN Pad is released, the actuator will stop in its current position and two LED
’
s will be dis-
played to show the approximate position of the actuator. Press the Close Pad and the actuator will move
in a CW direction and the LEDs will display Red.
Start position
Command signal applied
LED Status
OPEN
CLOSE
Rotates CW until arrives at the Closed
position or movement is stopped
Closed Position.
CLOSED
OPEN
Rotates CCW until arrives at the Open
position or movement is
stopped
Open Position.