![RIFT Actuators RIFT 200 Installation, Operation & Maintenance Instructions Manual Download Page 13](http://html1.mh-extra.com/html/rift-actuators/rift-200/rift-200_installation-operation-and-maintenance-instructions-manual_1460503013.webp)
13
CONTROL SYSTEM
This allows the actuator to be programmed to operate and move in a nonlinear movement when
control from an external source requires the actuator to manage the flow with the position of the
valve.
VALVE PROFILE
This function allows the actuator to be programmed to operate and move in a pattern similar to the
design profile of specialised valves. The RIFT® 200 actuator matches the flow similar to the design of
the valve
EXTRA OPTIONS IN DESIGN (or available with restrictions)
BESPOKE BRANDING
Housing cover colours, moulded logo etc.
The RIFT® 200 is designed to have external power permanently applied. The internal
anti
-
condensation heater is only functional when external power is applied, without external
power there is no protection against damage from condensation. Damage by condensation is
therefore not covered by the warranty.
Note: (not all speeds are available at all motor power values) PID values will need to be adjusted. Consult
your distributor or the RIFT manufacturers for advice.
ELECTRICAL CONNECTION
-
ACTUATOR FUNCTION
The RIFT® 200 has the capability to accept any externally applied voltage between the ranges 12
-
30vDC
(12
-
26vAC) and 85 to 300v AC 1ph (50/60Hz), or DC. Supply voltages are segregated at the actuator
’
s
10
-
pin terminal strip into a low voltage connection on Pins 8 –
10 (
up to 30v maximum) and high voltage
connections on Pins 1 –
4.
(See page 15 for wiring diagram)
Follow the wiring diagram appropriate to your functional requirement to ensure the correct connection
of power and control signaling to the RIFT® 200 actuator.
DO NOT connect high voltage supply to the low voltage connection points on the terminal strip
otherwise irreparable damage will result and damage so caused is not covered by the warranty.
The command signals set to the actuator to control its movement must NEVER allow ANY
external power to be applied to the OPEN and CLOSE contacts AT THE SAME TIME otherwise
irreparable damage will result and damage so caused is not covered by the warranty.
Ensure that each actuator has its own independent over
-
current protected switch or circuit
breaker fitted as close as possible to the actuator and clearly marked that it is the isolator for that
actuator.
Damage to the actuator resulting from excessive power being drawn through the actuator from
inter
-
connected devices, such as a pump for example, is not covered by the warranty.
You should not rely on the internal earth terminal as the only protective earth connection and
should ensure that the actuator has appropriate externally connected grounding protection.
Use cabling with the correct gauge and insulation to conform with the relevant local standards
and codes, and use appropriate conduit or cable glands and ensure that they are fitted in
accordance with the manufacturers
’
instructions to prevent water ingress via the cable glands.
Damage from water ingress via the cable glands is not covered by the warranty.