Maintenance / Inspection

6.1 

Opening the condensate trap and dismantling the float control assembly

 The condensate trap must be depressurized. Shut off 

the system before and after the condensate trap.

 Release any remaining pressure by loosening the 

control screw (6) by only a quarter turn.

 Dismantle the steam trap from the pipeline system. 

 Loosen the housing screw (4) evenly crosswise and 

take off housing cover (2).

 Unscrew the retaining screw (8) and take it off.

 Screw in the install bolt for ca. 3 turns. (Picture 6)

 With a few light strokes using plastic hammer on the 

front side of the install bolt to loosen the float control 
assembly (5) from its conic housing seat. (Picture 6)

 Screw out the install bolt completely. Remove the float 

control assembly (5). (Picture 6)

6.2 

Disassembling, cleaning and assembling the float control (Picture 7)

 After removing the cotter pin (p), the rotary valve (v) can be simply pulled out to 

the side.

 Clean the parts using, for example, benzine.

 Check the rotary valve (v) for wear along the sealing edge. If wear is detected, the 

support body (b) and the rotary valve (v) must be replaced. A thorough leakage test 
must be carried out by Rifox.

 During assembling ensure that the notch in the rotary valve (v) points to the punch 

mark on the support body (b) and the cotter pin (p) is inserted and secured again 
carefully.

 The float must be able to be moved up and down by hand easily.

6.3 

Installing the float control assembly and assembling the condensate trap (Picture 8)

 The float control assembly (5) is inserted into the conical housing seat with the supporting body. It must be ensured that 

the immersion tube is posioned vertically downwards. 

 Screw in the install bolt with the washer but NOT tighten it.

 Check and reposite the float, until the float is in the mittel of the housing 

(while the housing stands vertical).  

 Tighten the install bolt with 35Nm. (Float control unit 

will be drawn into its conical seat.)

 Screw out the install bolt. Check again whether the float is in the middle 

of the cover opening. 

 Screw in the Retaining screw (8). Tighten the Retaining screw (8) with 35Nm.

 Check the housing gasket (2) and replace it if it is damaged.

 Tighten the housing screw (4) evenly crosswise. Tightening torque

 according to Section 6.5.

6.4 

Care and maintenance

 In the case of a great risk of dirt accumulation, the housing, when it is depressurized, should be rinsed thoroughly from 

time to time. If necessary, the float control assembly (5) should also be checked and cleaned according to Section 6.2.

 The dirt, which has been accumulated in the housing, can be removed away by screwing off the screw plug (additional 

equipment).

 For special applications, it is advisable to install a separate upstream strainer.

b

p v

Picture 7

Plastic

hammer

Install bolt

Housing

Float control
assembly

Picture 6

      Install bolt Washer

Housing

Tube

Picture 8