12
ENGLISH
TECHNICAL DATA
KEY FOR READING
Example: VegA RMXA 25-40
VegA
= high ef
fi
ciency pump
RMXA
RMXA = single 180 mm centres pump
RMYA = single 130 mm centres pump
25
25 = threaded connection, nominal diameter 25
40
40 = nominal head in [dm]
Data
Connection voltage
1 ~ 230 V * 10 %, 50/60 Hz
Temperature class
TF 95
Protection class IP
See rating plate
Energy Ef
fi
ciency Index EEI *
See rating plate
Nominal connection diameter threaded connection)
DN 15, DN 25, DN 32
Water temperatures at max. ambient temperature of +40°C
-10 °C to +95 °C
Max. ambient temperature
da -10 °C a +40 °C
Max. operating pressure
6 bar
Minimum inlet pressure at +95°C
0,3 bar
* Reference value for the most ef
fi
cient circulation pumps: EEI
≤
0.20
SCOPE OF DELIVERY
• Pump
• Sealing rings
• Connector included (spare parts cod. 4R002410)
• Installation and operating instructions
DESCRIPTION AND FUNCTION
INTENDED USE
The circulation pumps in this series are designed for warm
water heating systems and similar systems with constan-
tly changing
fl
ow volumes. Approved
fl
uids are heating
water in accordance with VDI 2035, water/glycol mixture
at a mixing ratio of 1:1. If glycol is added, the delivery data
of the pump must be corrected according to the higher
viscosity, depending on the mixing ratio percentage.
Intended use of the pump/installation also includes fol-
lowing these instructions.
Any other use is not regarded as intended use.
PRODUCT DESCRIPTION
The pump (Fig. 1/1) consists of a hydraulic system, a
glandless pump motor with a permanent magnet rotor,
and an electronic control module with an integrated fre-
quency converter.
The control module has an operating knob together with
an LED display (Fig. 1/2) for setting all parameters and for
displaying the current power consumption in W.
FUNCTIONS
All functions can be set, activated or deactivated using the
operating knob.
Summary of Contents for VegA RMXA 25-40
Page 1: ...Cod 4177724 Ed 02 01 13...
Page 16: ...16 Fig 1 Fig 2a H max H H min Hs Q Hs 1 2 Fig 2b max H min 2 1 3 Q...
Page 17: ...17 Fig 3 Fig 4a Fig 4b PE N L...
Page 18: ...18 Fig 4c Fig 4d Fig 4e Fig 5...
Page 21: ...21...
Page 22: ...22 ITALIANO...
Page 23: ......