20017376
14
GB
Operation
The diaphragm is not required for the RX80 burner, but only the
valve adjustment.
The table suggests the adjustments of the control box for the un-
der mentioned models.
These values are approximate.
WARNING
Consider the letters of the Trimmers (Fig. 11) as
adjustment notches.
m a x
m i n
t a r
s
t
m
a x
t a r
s
t
m i n
0
1
2
3
4
5
6
0
1
2
3
4
5
6
0
1
2
3
4
5
6
Maximum output
Minimum output
Starting output
D9814
Fig. 11
Generator model X50
Adjustment of burner RX80S/PV operating with methane ( G20 )
WORK PHASE
ELECTRONIC ADJUSTMENT
TRIMMER POSITION
FAN VELOCITY
GAS VALVE
P2 PRESSURE
OUTPUT
symbol
Notch
Turns mbar
kW
MAXIMUM OUTPUT
trimmer max
o
1
5000
-1,1
61
STARTING OUTPUT
trimmer start
r
4
4900
-0,9
58
MINIMUM OUTPUT
trimmer min
o
1
1800
-0,1
22
Generator model X65
Adjustment of burner RX80S/PV operating with methane ( G20 )
WORK PHASE
ELECTRONIC ADJUSTMENT
TRIMMER POSITION
FAN VELOCITY
GAS VALVE
P2 PRESSURE
OUTPUT
symbol
Notch
Turns mbar
kW
MAXIMUM OUTPUT
trimmer max
o
5
6240
-1,7
76
STARTING OUTPUT
trimmer start
r
4
5000
-1
60
MINIMUM OUTPUT
trimmer min
o
1
1800
-0,1
22
Generator model X80
Adjustment of burner RX100S/PV operating with methane ( G20 )
WORK PHASE
ELECTRONIC ADJUSTMENT
TRIMMER POSITION
FAN VELOCITY
GAS VALVE
P2 PRESSURE
OUTPUT
symbol
Notch
Turns mbar
kW
MAXIMUM OUTPUT
trimmer max
o
5
6300
-3
98,5
STARTING OUTPUT
trimmer start
a
3
4400
-1,5
70
MINIMUM OUTPUT
trimmer min
m
2
2000
-0,15
31
Generator model X100
Adjustment of burner RX120S/PV operating with methane ( G20 )
WORK PHASE
ELECTRONIC ADJUSTMENT
TRIMMER POSITION
FAN VELOCITY
GAS VALVE
P2 PRESSURE
OUTPUT
symbol
Notch
Turns mbar
kW
MAXIMUM OUTPUT
trimmer max
o
5
6240
-4,6
122
STARTING OUTPUT
trimmer start
-
0
3500
-1,4
71
MINIMUM OUTPUT
trimmer min
m
2
2000
-0,15
31