GENERAL
9
b
When you finish installing the burner in the boiler,
fill the gap between the burner’s blast tube and the
refractory material in the door with the ceramic insu-
lation (A) supplied with the boiler.
45°
45°
A
A
Ø
BURNER PLATE
RTQ 3S
r
boilers have burner plates with holes
arranged to accept the recommended burners. The fol-
lowing table shows the dimensions of the holes.
PRODUCT IDENTIFICATION
b
If these plates or any other means of clearly identifying the product are defaced, removed or lost, proper installation
and servicing may be rendered difficult.
- Serial number plate
This is located on the boiler body and specifies
the serial number, model, and furnace power.
- Data plate
This lists the technical specifications and perfor-
mance of the product.
It comes inside the documentation envelope. On
completion of the installation you MUST apply it in
a clearly visible position at the top of one of the
side panels.
If you damage or lose this label, order a
replacement immediately from
r
’s Technical
Assistance Service.
The boilers are identified by two plates:
DIMENSIONS (mm)
RTQ 3S
35
55
70
Ø
110
110
140
A
106
106
120
Threads
M8
M8
M8
WEEK OF
MANUFACTURE
2 3
2 7
0 0 0 0 5 8 1
b
Blast tubes must not exceed the specified lengths
by more
than 20%
.
a
Do not re-use old burners if their blast tube lengths
are below those specified in the table.