TECHNICAL ASSISTANCE SERVICE
30
Proceed as follows to clean the boiler:
- Open the front door (1) and pull out the turbulators (2)
b
If you need to replace any turbulators, make sure
that the replacements have the characteristics list-
ed in the table below.
Clean the boiler and remove any carbon deposits from the surfaces of the heat exchanger
at least once a year
. This not
only extends the boiler’s working life, but also keeps it efficient in terms of heat output and consumption.
CLEANING THE BOILER
- Use a flue brush (3) or other suitable tool to clean inside
the combustion chamber and the flue gas pipes.
- Open the inspection window (4) and clean out any
deposits from inside the flue gas box.
If more thorough cleaning is required, remove the flue
gas box cover (5). Fit a new glass fibre seal when fitting
the cover again.
Check at regular intervals that the condensate drain (6)
is not blocked.
Clean all removed components, then follow the above
steps in the reverse order to refit them.
b
If you are using fuel oil burners with a smoke scale
reading higher than 3, perform the following actions
every 300 hours
of operation:
- Clean the boiler’s heat exchange surfaces.
- Check and clean the turbulators. Replace if worn
or damaged.