![Riello RS5F Installation, Use And Maintenance Instructions Download Page 35](http://html1.mh-extra.com/html/riello/rs5f/rs5f_installation-use-and-maintenance-instructions_1459899035.webp)
33
20141167
GB
Start-up, calibration and operation of the burner
6.1
Notes on safety for the first start-up
6.2
Adjustments prior to ignition
Check the adjustment of the head as shown in page 16.
Check that the air damper has been correctly adjusted.
Slowly open the manual valves situated upstream from the
gas train.
Adjust the air pressure switch to start of the scale.
Purge the air from the gas line.
We recommend using a plastic tube routed outside the
building and to purge air until gas is smelt.
6.2.1
Air damper setting
Do not carry out the first ignition with the air damper lower than
set point 1.
The air damper leaves the factory set for minimum output.
To vary the setting proceed as follows:
loosen the nut 9) (Fig. 11) and act on the screw 8)(Fig. 11).
When burner shuts down the air damper automatically close
still a max. chimney depressure of 0.5 mbar.
6.3
Gas pressure switch
6.4
Air pressure switch
The air pressure switch is set after all other adjustments have
been made. Begin with the switch at the start of the scale.
With the burner function at the required output, turn the knob
slowly in a clockwise direction until burner lockout.
Now turn the knob one notch anti-clockwise and repeat the
burner start-up to check everything is regular.
If the burner locks out again, turn the knob again by half a notch.
6.5
Combustion adjustment
In conformity with Efficiency Directive EN 676, the application of
the burner on the boiler, the adjustment and testing must be
carried out in compliance with the instruction manual of the boiler,
including control of the CO and CO
2
concentration in the flue
gases, their temperature and the average temperature of the
water in the boiler.
It is advisable to set the burner according to the type of gas used
and following the indications in Tab. S.
Tab. S
6
Start-up, calibration and operation of the burner
ATTENTION
The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and
regulations of the laws in force.
ATTENTION
Check the correct working of the adjustment,
command and safety devices.
CAUTION
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas
delivery at the minimum.
ATTENTION
To calibrate the gas pressure switch, refer to the
gas train manual.
ATTENTION
In conformity with the standard, the air pressure
switch must prevent the air pressure falling
below 80% of the adjusted value and the CO in
the flue gases exceeding 1% (10,000 ppm).
To check this, insert a combustion analyser in
the flue, slowly reduce the burner air setting (for
example with a piece of cardboard) and verify
that the burner locks out before the CO value in
the flue gases exceeds 1%.
EN 676
Excess air: max. output
1.2 – min. output
1.3
GAS
Theoretical max CO2
0 % O2
Setting CO2 %
CO
mg/kWh
NOx
mg/kWh
= 1.2
= 1.3
G 20
11.7
9.7
9.0
100
170
G 25
11.5
9.5
8.8
100
170
G 30
14.0
11.6
10.7
100
230
G 31
13.7
11.4
10.5
100
230