20141167
14
GB
Installation
5.4
Preliminary checks
Control of the supply
Control of burner characteristics
Check the identification label of the burner (Fig. 6), showing:
A
the burner model
B
the burner type
C
the cryptographic year of manufacture
D
the serial number
E
the data for electrical supply and the protection level
F
the electrical power consumption
G the data of the burner possible minimum and maximum
output (see Firing rate)
Attention.
The burner output must be within the boiler's
firing rate.
5.5
Operating position
CAUTION
After removing all the packaging, check the
integrity of the contents.
In the event of doubt, do not use the burner;
contact the supplier.
The packaging elements (cardboard box, clips,
plastic bags, etc.) must not be abandoned as they
are potential sources of danger and pollution; they
should be collected and disposed of in the
appropriate places.
ATTENTION
The figure of the label (Fig. 6) is indicative.
Some of the data may be arranged in a different
position.
ATTENTION
A burner label that has been tampered with,
removed or is missing, along with anything else
that prevents the definite identification of the
burner makes any installation or maintenance
work difficult.
R.B.L.
TIPO TYP
TYPE
II2ELL 3B/P DE
II2H3B/P
AT,CH,IS
II2H3 GB,IE,IT
N2L3B/P LU
GAS
GAZ
FAM.2
FAM.3
I2E(P)B.I3 BE
II2L3B/P NL
II2Er3P FR
Icc A
Imax A
PESO kg
RIELLO S.p.A.
I-37048 Legnago (VR)
A
B
F
B
G
D
E
C
Fig. 6
20098188
ATTENTION
The burner is set up to operate only in
positions
1
,
2
,
3
,
5
,
6
and
7
(Fig. 7).
Installation
1
is preferable, as it is the only
one that allows the maintenance operations
as described in this manual.
The installation layout illustrated in position
5
is only possible using the “MULTI-BLOC
rotation kit”, to be ordered separately.
DANGER
Any other position could compromise the
correct operation of the appliance.
Installation
4
are forbidden for safety
reasons.
Fig. 7
D4450
2
3
4
5
1
6
7