20027770
8
GB
Technical description of the burner
4.4
Technical data
Tab. A
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at test point 5) (Fig. 5) with zero pressure in the combustion chamber and maximum burner output.
(3)
Noise emission tests carried out as specified in EN 15036-1 with measurement accuracy
σ
= ± 1.5 dB, in the manufacturer’s combustion chamber
with burner operating on test boiler at maximum output.
4.5
Electrical data
Motor IE1
Motor IE2
Tab. B
Model
RS 650/E BLU
Output
(1)
Delivery
(1)
min - max
kW
kg/h
1430/3000 - 6550
121/253 - 552
Fuel
Natural gas: G20 (methane) - G21 - G22 - G23 - G25
Gas pressure at maximum delivery
(2)
Gas: G20/G25
mbar
58/86.5
Operation
Continuous / Intermittent
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperatur
°C
0 - 40
Combustion air temperature
°C max
60
Noise level
(3)
Sound pressure
Sound power
dB(A)
90.1
104.3
Modell
RS 650/E BLU
Type
1122T1
Electrical supply
V
Hz
3N ~ 400 +/-10%
50
Fan motor
rpm
V
kW
A
2950
400/690
18.4
35 - 20.5
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
Electrical power consumption
kW max
19.5
Electrical protection
IP54
Modell
RS 650/E BLU
Type
1122T1
Electrical supply
V
Hz
3N ~ 400 +/-10%
50
Fan motor
rpm
V
kW
A
2950
400/690
18.5
35.7 - 20.6
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
Electrical power consumption
kW max
20.8
Electrical protection
IP54
Summary of Contents for RS 650/E BLU