Technical description of the burner
3.1
Technical data
(1)
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394 ”wc - Altitude 329 ft.
(2)
Pressure at test point 21) (Fig. 5), with zero pressure in the combustion chamber, with open gas ring 2) (Fig. 21) at maximum burner output.
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
*
Firing rate for C-ETL Canadian Listing
3.2
Electrical data
Fan motor IE1
Fan motor IE2/EPACT
3
Technical description of the burner
Model
RS 200/E LN
Output
(1)
maximum
kW
MBtu/hr
1526 - 2664 (2422*)
5207 - 9090 (8264*)
minimum
kW
MBtu/hr
615
2100
Fuel
- max. delivery
- pressure at max. delivery
(2)
SCFH
“ wc
Natural gas
8917
11.3
Operation
Low - high or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Noise levels
(3)
dBA
83.1
Model
RS 200/E LN
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
460/3/60
Fan motor
rpm
HP
V
A
3480
7.6
460
9.7
Ignition transformer
V1 - V2
I1 - I2
120 V - 1 x 8 kV
1.6 A - 20 mA
Electrical power consumption
W
6550
Electrical control circuit consumption
W max
750
Total electrical consumption
W
7300
Electrical protection
NEMA 1
Model
RS 200/E LN
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
460/3/60
Fan motor
rpm
HP
V
A
3500
7.5
460
9.3
Ignition transformer
V1 - V2
I1 - I2
120 V - 1 x 8 kV
1.6 A - 20 mA
Electrical power consumption
W
6300
Electrical control circuit consumption
W max
750
Total electrical consumption
W
7050
Electrical protection
NEMA 1