Start-up, calibration and operation of the burner
27
20008113
GB
5.3
Burner start-up
Feed electricity to the burner via the disconnecting switch on the
boiler panel.
Close the thermostats/pressure switches and turn the switch of
Fig. 32 to position
“LOCAL”
.
Make sure that the lamps or testers connected to the
solenoids, or indicator lights on the solenoids them-
selves, show that no voltage is present. If voltage is
present, stop the burner
immediately
and check the
electrical wiring.
For the start-up procedure and the parameters
calibration, refer to the specific instruction
manual of the LMV37... electronic cam supplied
with the burner.
5.4
Final calibration of the pressure switches
5.4.1
Air pressure switch
5.4.2
Air pressure switch
The air pressure switch is connected in differential (Fig. 33) and is
activated by both the negative pressure of the air intake and the air
pressure from the fan.
Adjust the air pressure switch (Fig. 30) after having performed all
other burner adjustments with the air pressure switch set to the
min. of the scale.
With the burner operating at low fire, adjust the pressure switch by
slowly turning the relative knob clockwise until the burner locks out.
Then turn the knob counter-clockwise about 20% of the set point
and start-up the burner again to ensure the set point is correct.
If the burner locks out again, turn the knob counter-clockwise a little
bit more.
OFF
LOCAL
REMOTE
Fig. 32
D9286
DANGER
ATTENTION
Fig. 33
20048352