20160742
6
GB
Technical description of the burner
3.1
Burner models designation
3.2
Technical data
Tab. A
(1)
Reference conditions: ambient temperature 68 °F (20°C) - Barometric pressure 394” WC - Altitude 329 ft.
(2)
Pressure at test point 17)(Fig. 4, page 11) with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound power is
measured using the "Free Field" method, required by EN 15036 standard, and according to an “Accuracy: Category 3” measurement, as described in
EN ISO 3746.
3
Technical description of the burner
Model
Riello Code
RBNA Code
Voltage
Flame safeguard
RS 190/M TC FS1
20160257
20166104
208-230/3/60
Burner mounted
RS 190/M TC
20166105
460/3/60
Burner mounted
RS 190/M TC FS1
20160258
20166106
575/3/60
Burner mounted
Model
RS 190/M
Output
(1)
High
MBtu/hr
kW
4845 - 8673
1420 - 2542
Low
MBtu/hr
kW
1781
522
Fuel
Natural or propane gas
- Max. delivery
SCFH
8673
- Pressure at max. delivery
(2)
“WC
5.9
Operation
Low - High or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °c)
Combustion air temperature
°F max
140 (60 °c)
Noise levels
(3)
Sound pressure
Sound power
dB(A)
83.1
94.1
Weight (complete with packaging)
lbs
210