5.6
Securing the burner to the boiler
Separate the combustion head from the rest of the burner, as
shown in Fig. 12.
To do this, proceed as follows:
loosen the four screws 3) and remove the hood 1);
disengage the articulated coupling 7) from the graduated
sector 8);
remove screws 2) from the two slide bars 5);
remove the 2 screws 4) and pull the burner back on slide
bars 5) by about 100mm;
disconnect the probe and electrode cables, then slide off the
burner completely from the slide bars.
If the probe or electrode is not correctly positioned, you must:
remove the screw 1)(Fig. 13);
take out the inner part 2)(Fig. 13) of the head, and then cali-
brate them.
Once this operation (if necessary) has been carried out, fix the
flange 11)(Fig. 12) to the boiler plate, interposing the insulating
gasket 9)(Fig. 12) supplied.
Use the 4 screws supplied, with a tightening torque of 35 - 40 Nm,
after protecting their thread with anti-seizing products.
Provide an adequate lifting system.
WARNING
Before fixing the burner to the boiler, check
(through the opening of the blast tube) that the
probe and electrode are correctly positioned (see
Fig. 14).
10
0m
m
1
2
5
11
14
13
12
9
3
8
7
6
15
15
10
3
4
D8688
Fig. 12
WARNING
The seal between burner and boiler must be air-
tight: after the start-up, check there is no leakage
of flue gases into the external environment.
1
2
Fig. 13
D8689
Summary of Contents for RS 150/M
Page 2: ...Translation of the original instructions ...
Page 41: ...39 20054085 GB Appendix Electrical panel layout ...
Page 42: ...20054085 40 GB Appendix Electrical panel layout ...
Page 43: ...41 20054085 GB Appendix Electrical panel layout ...
Page 44: ...20054085 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20054085 GB Appendix Electrical panel layout ...
Page 46: ...20054085 44 GB Appendix Electrical panel layout ...