Installation
5.4
Operating position
5.5
Preparing the boiler
5.5.1
Boring the boiler plate
Pierce the closing plate of the combustion chamber, as in Fig. 11.
The position of the threaded holes can be marked using the ther-
mal insulation screen supplied with the burner.
5.5.2
Blast tube length
The length of the blast tube 12)(Fig. 12) must be selected accord-
ing to the indications provided by the boiler manufacturer, and in
any case must be greater than the thickness of the boiler door
complete with its refractory.
The available lengths are the ones indicated in Tab. I.
Tab. I
For boilers with a front flue gas passes 15)(Fig. 12) or flame in-
version chamber, a protection device in refractory material 13)
must be inserted between the boiler fettling 14) and the blast tube
12).
For boilers with a water-cooled frontal, a refractory lining 13)-14)
is not necessary unless expressly requested by the boiler manu-
facturer.
Tab. J
WARNING
The burner is designed to operate only in
positions
1
,
2
,
3
and
4
(Fig. 10).
Installation
1
is preferable, as it is the only
one that allows the maintenance operations
as described in this manual.
Installations
2
,
3
and
4
permit operation but
make maintenance and inspection of the
combustion head more difficult.
DANGER
Any other position could compromise the cor-
rect operation of the appliance.
Installation
5
is prohibited for safety reasons.
Fig. 10
2
3
4
5
1
D7739
Blast tube
Short
Long
RS 150/M
280mm
415mm
WARNING
This protective fettling must not compromise the
extraction of the blast tube.
mm
A
B
C
RS 150/M
195
275-325
M12
Fig. 11
D455
Summary of Contents for RS 150/M
Page 2: ...Translation of the original instructions ...
Page 41: ...39 20054085 GB Appendix Electrical panel layout ...
Page 42: ...20054085 40 GB Appendix Electrical panel layout ...
Page 43: ...41 20054085 GB Appendix Electrical panel layout ...
Page 44: ...20054085 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20054085 GB Appendix Electrical panel layout ...
Page 46: ...20054085 44 GB Appendix Electrical panel layout ...