27
20123781
GB
Start-up, calibration and operation of the burner
6.3
Burner start-up
Close the remote controls and position the selector 1)(Fig. 33) to
“
AUTO
”. Select the “
MANUAL
” mode on the display (for further
information refer to the relevant control box manual).
Make sure that the lights or testers connected to the solenoids, or
the pilot lights on the solenoids themselves, indicate that no volt-
age is present.
If voltage is present, stop the burner immediately and check the
electrical connections.
When the limit thermostat (TL) closes, the burner begins the
starting cycle.
1
EMERGENCY
STOP
0 AUTO
AUXILIARY
DEVICE ON
BURNER
LOCKOUT
FAN MOTOR
OVERLOAD
DISPLAY
Fig. 33