Start-up, calibration and operation of the burner
5.5
Adjustments before first firing (gas operation)
Adjustment of the combustion head has been illustrated on
page 28.
In addition, the following adjustments must also be made:
open manual valves up-stream from the gas train.
Purge the air from the gas line.
Adjust the min gas pressure switch (Fig. 48) to the start of the
scale.
Adjust the max gas pressure switch (Fig. 47) to the upper limit
of the scale.
Adjust the air pressure switch (Fig. 46) to the zero position of
the scale.
Fit a U-type manometer (Fig. 43) to the gas pressure test point
on the sleeve. The manometer readings are used to calculate
MAX. burner power using the Tab. J on page 34.
5.6
Burner start-up
Feed electricity to the burner via the disconnecting switch on the
boiler panel.
Close the thermostats/pressure switches.
Turn the switch to position
“LOCAL”
and turn the switch to position
“
OIL
” for oil operation and “
GAS
” for gas operation (Fig. 44).
NOTE:
for further information, please refer to the specific instruction
of the control box.
CAUTION
Before starting up the burner it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas delivery
at the minimum.
D3515
Fig. 43
DANGER
Make sure that the lamps or testers connected to
the solenoids, or indicator lights on the solenoids
themselves, show that no voltage is present.
If voltage is present, stop the burner
immediately
and check the electrical wiring.
WARNING
When the burner starts, check the direction of the
motor rotation, as indicated in Fig. 44.
As soon as the burner starts up, look at the cooling
fan of the fan motor and check it is rotating anti-
clockwise.
If this is not the case:
place the switch of Fig. 44 in position
“OFF”
and wait for the control box to carry out the
switch-off phase;
disconnect the electrical supply from the
burner;
invert the phases on the three-phase power
supply.
Fig. 44
D11461
OIL
GAS
OFF
S8362
OFF
REMOTE
LOCAL
S8366