![Riello RLS 300/E Installation, Use And Maintenance Instructions Download Page 10](http://html.mh-extra.com/html/riello/rls-300-e/rls-300-e_installation-use-and-maintenance-instructions_1459780010.webp)
20036644
8
GB
Technical description of the burner
Fan motor and pump motor IE2/EPACT
Fan motor and pump motor IE2/EPACT
Model
RLS 300/E
RBNA Code
C9131000
C9131010
C9131001
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
208 - 220/3/60
460/3/60
575/3/60
Fan motor
rpm
HP
V
A
3500
7.5
208 - 230
18.6
3500
7.5
460
9.3
3500
7.5
575
7.4
Pump motor
rpm
HP
V
A
3470
2
208 - 230
5.4
3470
2
460
2.7
3470
2
575
2.2
Ignition transformer
Oil
V1 - V2
I1 - I2
120 V - 2 x 5 kV
2.7 A - 30 mA
Gas
V1 - V2
I1 - I2
120 V - 1 x 8 kV
1.6 A - 20 mA
Electrical power consumption
W
8200
Electrical control circuit consumption
W max
750
Total electrical consumption
W
8950
Electrical protection
NEMA 1
Model
RLS 400/E
RLS 500/E
RBNA Code
C9132010
C9132001
C9133010
C9133001
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
460/3/60
575/3/60
460/3/60
575/3/60
Fan motor
rpm
HP
V
A
3510
10
460
11.5
3510
10
575
8.8
3545
20
460
23.5
3545
20
575
18.8
Pump motor
rpm
HP
V
A
3470
2
460
2.7
3470
2
575
2.2
3470
2
460
2.7
3470
2
575
2.2
Ignition transformer
Oil
V1 - V2
I1 - I2
120 V - 2 x 5 kV
2.7 A - 30 mA
Gas
V1 - V2
I1 - I2
120 V - 1 x 8 kV
1.6 A - 20 mA
Electrical power consumption
W
10200
9900
18350
18400
Electrical control circuit consumption
W max
750
Total electrical consumption
W
10950
10650
19100
19150
Electrical protection
NEMA 1
Summary of Contents for RLS 300/E
Page 2: ......
Page 50: ...20036644 48 GB Appendix Spare parts A Appendix Spare parts ...
Page 57: ......
Page 58: ......
Page 59: ......