22
SYMBOL
PROBLEM
POSSIBLE CAUSE
RECOMMENDED REMEDY
The burner does not start
No electrical power supply
Close all switches and check connections
A limit or safety thermostat/pressure switch open
Adjust or replace
Control box lockout
Release the control box
Control box fuse interrupted
Replace it
Incorrect electrical wiring
Check
Defective control box
Replace
No gas supply
Open the manual valves between meter and
train
Mains gas pressure insufficient
Contact your gas company
Minimum gas pressure switch fails to close
Adjust or replace
Air pressure switch in operating position
Adjust or replace
The servomotor contact does not intervene (closure
cam 0°)
Adjust the closure cam 0° or replace the servo-
motor
The burner does not switch
on, and the lockout appears
Flame simulation
Replace the control box
Faulty motor remote control switch
Replace
Defective electrical motor
Replace
Motor lockout
Release the thermal relay
The burner starts up but
stops at the damper maxi-
mum opening
The servomotor contact does not intervene (maxi-
mum cam opening)
Cam adjustment (maximum opening)
or replace the servomotor
The burner switches on, but
then stops in lockout
Air pressure switch does not switch owing to lack of air pressure:
Air pressure switch poorly adjusted
Adjust or replace
Pressure switch pressure point pipe blocked
Clean
Poorly adjusted head
Adjust
Dirty fan
Clean
High depression in the furnace
Contact our Technical Department
The burner turns on and
then remains in lockout
mode
Failure to the flame detection circuit
Replace the control box
The burner remains in pre-
purging phase
The servomotor contact does not intervene (mini-
mum cam)
Cam adjustment (minimum)
or replace the servomotor
Once the pre-purging and
the safety time has elapsed
the burner goes into lockout
without the flame appearing
Gas pressure too low
Increase pressure at governor
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
Faulty or grounded high voltage cable
Replace
High voltage cable deformed by high temperature
Replace and protect
Faulty ignition transformer
Replace
Incorrect valve or ignition transformer connections
Redo them
Defective control box
Replace
A closed valve upline the gas train
Open
Air in pipework
Bleed air
Lockout with flame appear-
ing
The VS or VR solenoids let too little gas through
Increase
Dirty flame sensor
Check, replace flame sensor
Faulty connection
Check, replace flame sensor
Insufficient detection current
(min. 6 µA)
Measure current, replace flame sensor
Flame sensor exhausted, faulty
Replace
Maximum gas pressure switch intervention
Adjust or replace
Defective control box
Replace
The burner continues to re-
peat the start-up cycle, with-
out lockout
The gas pressure in the gas mains lies very close to
the value to which the minimum gas pressure switch
has been set.
The sudden drop in pressure after valve opening
causes temporary opening of the pressure switch it-
self, the valve immediately closes and the burner
comes to a halt.
Pressure increases again, the pressure switch clos-
es again and the ignition cycle is repeated.
The sequence repeats endlessly.
Reduce the minimum gas pressure switch inter-
vention pressure.
Replace the gas filter cartridge
Lockout without symbol indi-
cation
Flame simulation
Replace the control box
P
1
Summary of Contents for RLS 190/M MZ
Page 2: ...Original instructions 说明书原文翻译 ...
Page 28: ...26 0 11 1 2 3 13 45 45 67 67 8 1 1 2 9 13 11 1 2 1 ...
Page 29: ...27 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 59: ...25 0 11 1 2 3 13 45 45 67 67 8 1 1 2 9 13 11 1 2 1 ...
Page 60: ...26 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 66: ......
Page 67: ......