20146383
6
GB
Technical description of the burner
3.1
Technical data
Tab. A
(1)
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” wc - Altitude 329 ft.
(2)
Related to G.C.V.
(3)
Pressure at test point 13)(Fig. 5, pag. 11), with zero pressure in the combustion chamber, and maximum burner output.
(4)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated
output.
(*)
Firing Rate for C-ETL Canadian Listing
3.2
Electrical data
Tab. B
3
Technical description of the burner
Model
RLAS 1000/EV
(FGR prepared)
RLAS 1200/EV
(FGR prepared)
Output delivery
(1)
High
Natural
Gas
MBtu/hr
(2)
14.000
39.780
35.800
*
20.500
43.000
38.700
*
#2
GPH
100
284
255
*
146.4
307
276.4
*
Low
Natural
Gas
MBtu/hr
(2)
-
-
-
4.300
-
-
#2
GPH
-
-
-
30.7
-
-
Fuel
Oil #2
Natural gas
- Gas max. delivery
SCFH
39.386
42.574
- Gas pessure at max. delivery
(3)
“WC
30.1
36.8
Operation
Low - high or modulating
Nozzles
1
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40°C)
Combustion air temperature
°F max
140 (60°C)
Noise levels
(4)
dBA
80
90
Model
RLAS 1000/EV
(FGR prepared)
RLAS 1200/EV
(FGR prepared)
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
460/3/60
Fan motor
IE3/NEMA Premium Efficiency
rpm
HP
V
A
3540
30
460
35.8
3530
40
460
49.8
Pump motor
IE3/NEMA Premium Efficiency
rpm
HP
V
A
3500
2
460
2.8
3500
2
460
2.8
Ignition transformer (GAS)
V1 - V2
I1 - I2
120 V - 1 x 8 kV
1.6 A - 20 mA
Electrical power consumption
W
25670
34235
Electrical control circuit consumption
W max
1250
1250
Total electrical consumption
W
26920
35485
Electrical protection
NEMA 3
Minimum Circuit Ampacity (MCA)
A
47
62
Maximum rating of overcurrent
protective device (MOP)
A
84
112
Summary of Contents for RLAS 1000 EV
Page 2: ...Original instructions ...
Page 50: ...20146383 48 GB Appendix Spare parts A Appendix Spare parts ...
Page 54: ......