27
20141254
GB
Start-up, calibration and operation of the burner
6.12 Programming menu
GENERAL
The programming menu can be accessed via the integrated reset
button during OPERATION and in STAND-BY.
If in page menu the reset button is not pressed within 10 seconds
the page will be automatically be exited and there will be a green
led flashing for the time set.
If the number of presses on the reset reset button exceeds the
maximum allowable, the value that stays in memory will be the
maximum one.
If the reset button is pressed for more than 60 seconds, a button
error will be displayed and the control-box will restart.
BLOCK DIAGRAM FOR ENTERING THE MENU
Tab. H
Function
Button
release time
No. of blinks of
the led per
menu page
No. of pressings
of the reset button
No. of blinks of
the Led (green)
Quitting the menu
Shut-down test
5s
t < 10s
2 blinks
RED
/
none
/
none
Automatic, at the
end of the blinking
Post-
purging
10s
t < 15s
1 blink
GREEN
1 = 10 sec.
2 = 20 sec.
3 = 30 sec.
4 = 60 sec. (default)
5 = 120 sec.
6 = 0 sec. (deactivated)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
10 sec. after the release of
the button
Intermittent
operation
20s
t < 25s
3 blinks
GREEN
1 = 0 disabled
2 = 1 hour
3 = 24 hours (default)
1 blink
2 blinks
3 blinks
10 sec. after the release of
the button
Last lockout
memorised
25s
t < 30s
4 blinks
GREEN
/
none
Displaying the type
of lockout accord-
ing to the table sec-
tion 6.9.2
10 sec. after the release of
the button
S9278
OPERATION (WITH FLAME) AND STAND-BY
OPERATION
INTERMITTENT
POST
OPERATION
2 RED
1 GREEN
3 GREEN
OUTLET
AUTOMATIC
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
SWITCHING OFF
PURGING
20 SEC.
LAST LOCKOUT
MEMORISED
25 SEC.
4 GREEN
10 SEC. AFTER
RELEASE
5 SEC.
10 SEC.
BURNER STATE
TYPE OF
FUNCTION
NUMBER
OUTLET
OF BLINKS
Fig. 20