35
COMMISSIONING AND MAINTENANCE
EEPROM CONTROL
The burner controller automatically checks for errors in the
microcontroller EEPROM and enters lockout if an error is
detected. An error is indicated by the LED flashing (see the “Fault
diagnosis - lockouts” section on page 30).
DEACTIVATION OF AUTOMATIC PRE-HEATING
The automatic pre-heating functioning can be deactivated by
pressing the reset or remote reset button.
Pre-heating remains de-activated until:
− a lockout occurs;
− mains power fails or is switched off;
− the boiler shuts down for a controlled shutdown and
restart.
Pre-heating de-activation sequence
Colour of
button LED
Only de-activate the pre-heating if no lockout
or errors are present
-
Deactivate the pre-heating by means of the
reset or remote reset button.
-
Switch on the burner and simultaneously hold
down the reset or remote reset button for 3
seconds.
RED
Release the reset or remote reset button
within 3 seconds.
OFF
The burner will de-activate pre-heating only
if the reset or remote reset button is released
within 3 seconds.
-
The deactivation of the automatic pre-heating function is not
lost if the switching off test function is active or if the heat
request thermostat opens.