USER
9
If the problems persist, proceed as follows to make sure
that the flue gas thermostat has not tripped.
- Wait about 5 minutes, then remove the cover from the
flue gas thermostat reset button (8) and push the button.
- Wait for the burner to complete the entire start-up cycle
again, up to the ignition of the flame.
b
If the flue gas thermostat trips repeatedly, make
sure that the flue gas vent pipe is not blocked and
that the flue has been installed correctly.
b
No warning signal is given if the safety thermostat
trips, but the fact that is has tripped can be seen
from the boiler temperature gauge (T>110°C).
Proceed as follows to reset the safety thermostat:
- Wait until boiler temperature falls below 80°C.
- Remove the safety thermostat cover.
- Press the manual reset button.
- Wait for the burner to complete the entire fuel pre-
heating and start-up cycle again, up to the ignition of
the flame.
20
40
60
80
100
0
120
8
Summary of Contents for INSIEME CONDENS 26 B
Page 1: ...INSTRUCTION FOR THE USER CONDENSING BOILERS 26 B 26 BK 35 B 35 BK 26 BK 35 BK 26 B 35 B ...
Page 13: ...USER 13 ...
Page 14: ...USER 14 ...
Page 15: ......