Preparation for start up
5.6
Flame present check
Minimum current for correct working is 70 µA.
If the value is lower, it could be due to:
•
exhausted photocell;
•
low current (lower than 187 V);
•
bad regulation of the burner.
In order to measure the current, use a microammeter of 100
A c.c., connected in series to the photocell, as in the scheme, with
a capacitor of 100
F - 1V c.c. at the same level of the instrument
5.7
Periodic checks
We recommend carrying out the following checks:
LIST OF MONTHLY CHECKS
1
Verify the photocell and possibly clean it.
2
Check the ignition device and clean if necessary.
3
Check the right pressure levels for fuel and air.
4
Check the correct movement and setting of the air damper and relative lifting assemblies.
5
Check the start up sequence and the safety interlocks, by simulating the relative anomaly situation.
LIST OF YEARLY CHECKS
1
Check the fuel blocking valves are still well sealed.
2
Check the settings on the pressure switches.
3
Visual check of the wires and connectors.
4
Check and clean the pressure test points.
5
Check the installation pipes for leaks.
6
Visual check of any damage and/or deformation of the following components:
- cylinder/distributor unit;
- flame disc;
- ignition electrodes;
- flame pipes.
D1143
Fig. 23
Summary of Contents for DB3 SM C01 TC FS1 A0 T250
Page 2: ......
Page 22: ......
Page 42: ......
Page 43: ...1...
Page 52: ...10 3 3 4 12 1 2 3 9 10 13 12 1 1 2 5 4 3 3 20084515 12...
Page 53: ...11 4 4 1 D7543 C GF HPG LPG MM PA PGM PGm RG SRV VE VPS VR VS 0 5 4 bar 500 mbar 13...
Page 54: ...12 4 4 2 D9135 MB PA PGM SM UV UV TA TB...
Page 56: ...14 5 5 3 1 4 2 3 5 6 7 1 2 0 3 20 4 5 20 130 1 4 5 4 130 19 18 D1500 3 2 4 1 19 1 2 3 4 D1499...
Page 57: ...15 5 MAN 3 1 130 90 2 19 2 19 20 2 2...
Page 59: ...17 5 5 6 70 A 187 V 100 A c c 100 F 1V c c 5 7 1 2 3 4 5 1 2 3 4 5 6 D1143 23...
Page 60: ...18 6 6 1 1 2 3 VR VR VS VR...
Page 61: ...19 6...
Page 62: ......
Page 63: ......