Riello Condexa Pro2 150 Evo IN A Installation Instructions Manual Download Page 25

25

ADJUSTING THE FUNCTIONAL PARAMETERS

Low load

The low load function prevents burner ignition and shut off in 

the case of a low heat demand. The conditions for low load op-

eration activation is controlled in every Slave card that sends the 

function activation request to the Master.

During normal operation, the setpoint of the active circuit (high 

or low temperature circuit setpoint or DHW setpoint) is sent to 

the Slave cards and is controlled by the temperature of the heat-

ing element by every Slave card:

if the modular system temperature > Setpoint – 8°C or

if the modular system temperature >  85°C - 8°C

consent for starting the burner is not given.

If the Slave board acquires a modular system temperature great-

er than 85°C for 3 times with the burner ignited, the heating el-

ement is turned off and the ignition procedure is started again.

Emergency function

In the case of a Master card fault, there are two methods for 

manually controlling the Slave cards:

 

− With eBUS and with the manifold sensor

 

Disconnect the power supply from the system, disconnect 

the BUS. Set the address 000000 on all slave cards (J10 

and J17 OFF). Connect a power supply between 21 and 28 

Vac to the BUS.

 

If the manifold temperature < Temp.Emergency (Par.40; 

preset  70°C;  can  be  set  between  10  and  80°C)  all  the 

burners will operate at maximum power.

 

If the manifold temperature > Temp.Eme 5°C all 

burners are off.

 

− With PC

 

Disconnect the system power supply, disconnect the BUS 

and connect the PC interface. The burner power can be 

sent to the Slave card directly with the PC.

 

9

In  the  case  of  error,  contact  Technical  Assistance  Service. 

R

.

Heat  demand  management  for  the  high  temperature  circuit 

with analogue input (Par. 14=2 or 3)

The room thermostat for the high temperature circuit is ignored 

in the case of heat demand and the input signal is used for cal-

culating the system setpoint temperature or power.

The analogue input (see terminals 13-14 on the wiring diagram 

on page 35) is only for the Master card and can also be used for 

the low temperature circuit (Par.22). The analogue input cannot 

be used for both circuits.

ANALOGUE POWER INPUT, Par. 14=2 (Par. 22=2 for low tempera-

ture circuits)

The following rules apply to high temperature (low temperature) 

circuit demand:

0-2Vdc:

  no demand by the high temperature (low temperature) 

circuit

2-9Vdc:

 the heat demand is converted into a power demand 

for each Slave. A 2V input corresponds to minimum power, 9V to 

maximum power (Par.15). The power is calculated linearly be-

tween 2V and 9V. Hysteresis for the end of demand is 0.2V and 

therefore demand is present above 2V and stops below 1.8V.esta 

è presente sopra i 2V e cessa sotto 1,8V.

Voltage (Volts)

0

1

2

3

4

5

6

7

8

9

10

Power (kW)

50

100

150

200

250

Figure 23   

The burner ignited when:

 

− Delivery temp. 

 Setpoint_ch_high (Par.1) – Ch_high_hist_

on (Par.19)

 

− (Delivery temp. 

 Setpoint_ch_low (Par.3) – Ch_low_hist_

on (Par.26)

 

The burner shuts off when:

 

− Delivery temp. > Setpoint_ch_high (Par.1) + Ch_high_hist_

off (Par.20)

 

− (Delivery temp. > Setpoint_ch_low (Par.3) + Ch_low_hist_

off (Par.27)

ANALOGUE TEMPERATURE INPUT, Par. 14=3 (Par. 22=3 for low tem-

perature circuits)

The following rules apply to high temperature (low temperature) 

circuit demand:

0-2Vdc:

  no demand by the high temperature (low temperature) 

circuit

2-9Vdc:

 the heat demand is converted into a power demand 

for each Slave, using the algorithm PID_CH_high (PID_CH_

low). 2V corresponds to a setpoint equal to T_Ch_high_

foot,  Par.  18  (T_Ch_low_foot,  Par.  24),  9V  to  a  setpoint 

equal to SetPoint_Ch_high, Par.1 (SetPoint_Ch_low, Par.3). 

The  setpoint  is  calculated  linearly  between  2V  and  9V. 

Hysteresis for the end of demand is 0.2V and therefore 

demand is present above 2V and stops below 1.8V.

Voltage (V)

0

1

2

3

4

5

6

7

8

9

Setpoint

10

20

30

40

50

60

70

80

90

10

Figure 24  

The burner ignited when:

 

− Delivery temp. 

 Setpoint_ch_high (Par.1) – Ch_high_hist_

on (Par.19)

 

− (Delivery temp. 

 Setpoint_ch_low (Par.3) – Ch_low_hist_

on (Par.26)

The burner shuts off when:

Summary of Contents for Condexa Pro2 150 Evo IN A

Page 1: ...cod 20094445 rev 5 12 2015 Condexa Pro2 EVO EN INSTALLATION INSTRUCTIONS...

Page 2: ...supply 12 6 2 Electrical connections 12 6 2 1 Connection to mains 12 6 2 2 Connection to thermoregulators 12 6 2 3 Connection to pumps 13 6 2 4 Connection to room thermostats on off 14 6 2 5 Connecti...

Page 3: ...weather conditions after it has been unpacked anyhow to temperatures below 4 C or above 40 C until it has been connected up to the water gas and electricity mains so as to be able to activate the fros...

Page 4: ...ion for both single 0 0It is forbidden to obstruct the condensate drain 0 0It is forbidden to pull detach twist the wiring coming out of the heating unit even if unplugged from the power supply 0 0It...

Page 5: ...o the system in parallel posi tion as compared to the others through a flow return gas flue manifold and condensate discharge manifold According to the heat demand the regulation system switches on an...

Page 6: ...Fan 6 Return detection tap 7 Pump or 2 way valve 8 Control panel 9 Return probe 10 Exhaust flue probe 11 Water differential pressure switch 12 Gas valve 13 Ignition electrode 14 Automatic vent valve 1...

Page 7: ...o 92 42 EEC Directive Max pressure and temperature Pms NOx class NOx Figure 6 0 0It is forbidden to remove or mishandle the identification plates markings and any other making it difficult to safely i...

Page 8: ...o evenly dis tribute the limited quantity of initial lime scale 9 9A flushing cycle must be programmed after the plant has been installed to flush out any installation debris 9 9Water used for filling...

Page 9: ...installation can vary according to specific requirements of space or to the type of the installation itself e g leaned against the wall back to back etc in any case make sure that same necessary spac...

Page 10: ...s of each unit and in some points of the hydraulic system specific for this purpose For more information on the characteristics of hydraulic system see 5 Installation diagrams in which different types...

Page 11: ...ly be adapted to the man ufacturing characteristics of the relevant heating unit with the purpose of exploiting the boiler potentials to the full and main tain the entire installation efficient for as...

Page 12: ...should break call in qualified personnel to replace it Always re fer to the data given in the diagrams in this handbook for operations of an electrical nature Remember that R is not to be held liable...

Page 13: ...ower on circulators external devices directly from the network with no electrical load passing through the fuse of the board Moreover in case of emergency mode the manual device 0 1 AUTO controls the...

Page 14: ...14 related to the Ch1 high temperature system and 22 Ch2 low temperature system are in fact in default and set in weather function Should one not want to connect the probe the boiler must be made to...

Page 15: ...t upper water manifold is equipped with two pock ets where the temperature probe has to be inserted The latter probe continuously checks the flow temperature of the heating circuit Either you are inst...

Page 16: ...show the flow temperature e g T1 80 C Adjust combustion by the screws shown in Figure 17 until reaching the rated CO2 value see table turning the screws clockwise to reduce the value N B Turn an ti c...

Page 17: ...ons activated by pressing a button or combination of two buttons pressed together Furthermore each button has a specific function depending on the selected user mode Figure 20 BUTTON KEY DESCRIPTION S...

Page 18: ...e values and operating status of the various circuits Press the button to scroll forward and view the values set for the individual circuits The values listed below will be displayed in succession by...

Page 19: ...oint to the desired value e g 40 C 5 Press OK to memorize the new value 6 After 3 secs the display will return to the display mode with the new setpoint If there is no change after pressing Set esc fo...

Page 20: ...to view and change the user and installer parameters Procedure for accessing the programming mode POS PROCEDURE DISPLAY 1 Manifold delivery temperature T1 e g T1 80 C 2 Press Set esc and OK After 5s t...

Page 21: ...ated for identifying the errors POS PROCEDURE DISPLAY 1 The display starts to flash to indicate one or more errors 1 b Press the address of the first unit will appear on the display alternating with t...

Page 22: ...limit preset to 80 C 100 90 80 T_CH_High_foot 70 T_out_min 60 50 T_out_max 40 30 20 10 0 25 20 15 10 5 0 5 10 15 20 T_CH_High Delivery temperature C CLIMATIC CURVE HIGH TEMPERATURE CIRCUIT HEATING RE...

Page 23: ...mperature Setpoint shut off hysteresis The setpoint in this case coincides with the value set for param eter 1 Setpoint_t_ch_high if the high temperature thermostat contact is closed whereas it is cal...

Page 24: ...es the Master control unit can only add a new burner when another is on If the Master control unit must increase the number of ignited burners first check that the next burner can be ignited no er ror...

Page 25: ...temperature or power The analogue input see terminals 13 14 on the wiring diagram on page 35 is only for the Master card and can also be used for the low temperature circuit Par 22 The analogue input...

Page 26: ...od of time equal to half the value set in Par 29 Time s Collector temperature Figure 25 Temperature Flow Mix C 20 30 40 50 60 Closing Opening Valve s 4 3 2 1 0 1 3 25 35 45 55 2 Open Close default Par...

Page 27: ...30 1 255 Setpoint of power supplied in hot water mode 8 h w max T 60 C 10 C 80 C Max value hot water setpoint 9 h w Priority 0 0 2 Hot water system priority 0 1 Hot water functioning with heating unti...

Page 28: ...r valve stand by differential 33 Power control 1 0 1 0 power distributed over min number burners 1 power distributed over max number burners 34 Pump mode 0 0 1 Third pump setpoint 0 Main pump of syste...

Page 29: ...32 33 Slaves not present Check that the bipolar switches of the individual units are ON Check the addresses on the slave Check the slave BUS connection Replace the Master card Replace the Slave card E...

Page 30: ...It was pressed more than 7 times in 30 min Wait for the error to disappear If the error did not disappear after max 40 min re place the Slave card E35 35 Water differential pressure switch error cont...

Page 31: ...J14 1 R1 4 3 T1 o t o m e r r t n o c s u b E o t o m e r r t n o c V 4 2 1 c r i c A T 2 c r i c A T 2 4 J1 PC E D O C R A B C T N 1 1 1 1 J 2 c r i c d n a m C T N 1 c r i c d n a m C T N C T N Pol...

Page 32: ...n 2 3 4 J6 J14 J15 J2 F1 J8 J7 3 1 5 a 1 2 3 m gv gv 4 gv 1 T1 6 5 J6 a 5 m J2 3 2 1 4 gv 1 T1 Slave n 1 J3 2 3 1 J16 m a TO MAIN POLO GROUND TO MAIN POLO GROUND PUMP GROUND GROUND GROUND NEUTRAL PHAS...

Page 33: ...ate production per hour 100 50 30 C with G20 gas kg h 22 4 33 6 44 8 Efficiency at rated power 80 60 C 98 1 98 1 98 1 Efficiency at rated power 50 30 C 108 1 108 1 108 1 Efficiency at min power 80 60...

Page 34: ...fficiency in DHW mode WH Daily electrical energy consumption Qelec kWh Daily fuel consumption Qfuel kWh Annual electrical energy consumption AEC kWh Annual fuel consumption AFC GJ 14 WATER IN CENTRAL...

Page 35: ...rms to require ments If the quality of water fails to conform to requirements either recondition the old water or separate the water circuits water in the boiler circuit must conform to requirements 3...

Page 36: ...go VR Tel 0442630111 Fax 044222378 www riello it As part of the company s ongoing commitment to perfecting its range of products the appearance dimensions technical data equipment and accessories may...

Reviews: