23

FAULT

PROBABLE CAUSE

No pre-heating of fuel

¥ No power

¥ Burner/Bag disconnected from each other.

¥ Adjustment or safety control device is open

¥ Faulty high point thermostat 5)(Fig.4)

¥ High point thermostat with reset push-button 6)(Fig.4) has operated

¥ Heating elements contactor failed

¥ Oil pressure switch 7)(Fig.4) open due to lack of or insufÞcient loop pressure

¥ Faulty Pt 100 probe or temperature controller 

¥ Faulty temperature controller transformer

InsufÞcient pre-heating

¥ Tank heating elements interrupted

¥ Incorrectly set electronic thermostat

Pump not starting, when the temperature (approx.70

°

C) 

is reached on the low point thermostat 4)(Fig.4). 

¥ Faulty low point thermostat (not enabling)

¥ Pump motor thermal relay lock-out

¥ Faulty contactor

¥ Faulty pump

Burner not starting when SET2 temperature is reached.

¥ Temperature controller either faulty or with incorrect parameters

¥ Locked-out fan motor thermal relay

¥ Faulty capacitor (RN28)

¥ Faulty servomotor not going into 1st stage

Burner starting and then shutting down by lock-out.

¥ Short-circuited photocell

¥ Foreign light, ßame simulation

Hydraulic circuit not pressurising with consequent lock-

out at ignition.

¥ Valve 12)(Fig.4) not closing (coil interrupted, pre-heating element not operat-

ing)

Lock-out at ignition.

¥ Dirty or misshapen nozzle

¥ Incorrectly adjusted electrodes

¥ Faulty high voltage cables

¥ Faulty ignition transformer 

¥ Fan motor thermal relay tripped

¥ 1st stage solenoid-valve on nozzle holder not opening

¥ Fuel leaking out of pistons 3)(Fig.35) preventing them from opening

¥ Faulty photocell or control box

¥ InsufÞcient pressure or temperature

¥ Flame detachment due to excessive air

Burner not passing to 2nd stage

¥ 2nd stage thermostat open

¥ Faulty or incorrectly set servomotor

¥ Servomotor cam III incorrectly positioned

¥ 2nd stage solenoid-valve on nozzle holder not opening

¥ Fuel leaking out of pistons 3)(Fig.35) preventing them from opening

Shut down during operation.

¥ Oil pressure switch 7)(Þg.4) tripped

¥ High or low point thermostat tripped

Lock-out during operation and attempt to repeat the 

cycle.

¥ Pump or fan motor thermal relays tripped (RN 38 - RN 50)

¥ Flame detachment due to poor atomising or excessive air

Dirty combustion head.

¥ Dirty or misshapen nozzle

¥ Incorrect spray angle (45

°

 preferable)

¥ Incorrectly adjusted combustion head

¥ InsufÞcient air for combustion

¥ Low oil temperature

GB

Summary of Contents for bag 40

Page 1: ...use and maintenance instructions Bruciatori di nafta Heavy oil burners Funzionamento bistadio Two stage operation 2915585 4 98 CODICE CODE MODELLO MODEL TIPO TYPE 3433200 RN 28 633 T1 3433300 RN 38 63...

Page 2: ...a stessa compreso il controllo della concentrazione di CO e CO2 nei fumi della loro temperatura e di quella media dell acqua della caldaia I CONTENTS TECHNICAL DATA pagina 3 Packaging 4 Max dimensions...

Page 3: ...NTILATORE rpm W V A 2800 250 220 240 2 1 2800 450 220 240 380 415 2 1 2 2800 650 220 240 380 415 3 0 1 7 MOTORE ELETTRICO POMPA rpm W V A 1400 250 220 240 380 415 1 55 0 9 RISCALDATORI W 2800 4200 420...

Page 4: ...er il collegamento elettrico 18 Collettore BURNER DESCRIPTION Fig 3 1 Combustion head 2 Screw for combustion head adjustment 3 Photocell for ame presence control 4 Screw for xing fan to ange 5 Slide b...

Page 5: ...Passacavi per collegamento elettrico RN 28 3 Passacavi per collegamento elettrico RN 38 RN 50 4 Tubo per applicazione BAG sulla sinistra 1 Ugelli 2 Istruzione 1 Catalogo ricambi 1 BAG DESCRIPTION Fig...

Page 6: ...a di combustione bassa con scarsa miscelazione aria combustibile WORKING FIELDS Fig 5 1st stage DELIVERY must not fall below minimum values of the working eld 2nd stage DELIVERY must be selected in ar...

Page 7: ...STALLATION BOILER PLATE Fig 6 Drill the combustion chamber locking plate as shown in Fig 6 The position of the threaded holes can be marked using the thermal screen supplied with the burner BLAST TUBE...

Page 8: ...ell installatore The responsibility of the installer IMPIANTO IDRAULICO Di serie su bruciatore e Bag Standard for burner and Bag HYDRAULIC SYSTEM ALIMENTAZIONE COMBUSTIBILE Fig 12 Impianto ad anello i...

Page 9: ...li sulla presa dello stesso non darebbe il consenso per mancanza di pressione sarebbe opportuno sostituirlo con un vacuometro si ricorda che la pompa non pu superare una depressione massima di 4 m 35...

Page 10: ...rigid tubes are used the burner cannot be opened on the guides therefore the guides have to dismantled for burner maintenance The pumping and pre heating unit BAG may be located further than the supp...

Page 11: ...CO eseguito in fabbrica ELECTRICAL EQUIPMENT factory made RN 28 BAG 40 COLLEGAMENTO ELETTRICO a cura dell installatore ELECTRICAL CONNECTION eld made RN 28 Fig 16 COLLEGAMENTO ELETTRICO a cura dell in...

Page 12: ...CO eseguito in fabbrica ELECTRICAL EQUIPMENT factory made RN 38 BAG 40 COLLEGAMENTO ELETTRICO a cura dell installatore ELECTRICAL CONNECTION eld made RN 38 Fig 19 COLLEGAMENTO ELETTRICO a cura dell in...

Page 13: ...e RN 50 BAG 50 COLLEGAMENTO ELETTRICO a cura dell installatore ELECTRICAL CONNECTION eld made RN 50 Fig 22 COLLEGAMENTO ELETTRICO a cura dell installatore ELECTRICAL CONNECTION eld made BAG 50 Fig 23...

Page 14: ...tadio V2 Elettrovalvola di 2 stadio NOTA Per avere lo sblocco a distanza collegare un pulsante NA fra il mor setto 4 e il neutro dell apparecchiatura morsetti 15 16 17 e 18 ELECTRICAL SYSTEM KEY TO LA...

Page 15: ...del rel termico non comprende l assorbi mento di targa del motore a 400 V la protezione assicurata lo stesso CALIBRATION OF THERMAL CUT OUT Fig 24 This is required to avoid motor burn out in the even...

Page 16: ...ttachment G 1 2 2 Return G 1 2 3 Pressure gauge attachment G 1 8 4 Delivery 5 Pressure adjustment A Min delivery rate at 20 bar pressure B Delivery pressure range C Max suction depression D Viscosity...

Page 17: ...mente il tasto il led OUT1 lampegger e sul display verr visualizzato il SET1 impostato Per modi carlo agire sui tasti e Nella situazione con il SET1 premere brevemente il tasto il led OUT2 lampegger...

Page 18: ...umentare questa regolazione Camma II Regolata in fabbrica a 60 Regola la posizione della serranda aria in 2 stadio segue il servomotore solo in apertura Per diminuire l angolo passare in 1 stadio dimi...

Page 19: ...int thermostat 4 Fig 4 is reached time t1 the BAG pump is started and the oil is circulated and pre heated When the SET2 temperature set on the electronic thermostat is reached the burner control box...

Page 20: ...soste prolungate non togliere tensione al bruciatore ma fermarlo dalla serie termostatica Se necessario togliere tensione ripristinarla 1 2 ora prima di accendere il brucia tore CHECKS AND MAINTENANCE...

Page 21: ...ura o malfunzionamento del bruciatore KIT PRECIRCOLAZIONE OLII DENSI Questo kit agendo sul preriscaldatore e sulla pompa della BAG permette di mantenere a bruciatore spento la temperatura del com bust...

Page 22: ...va in pressione con conseguente blocco all accensione Non chiude la valvola 12 Fig 4 bobina interrotta resistenza di preriscaldo non funzionante Blocco all accensione Ugello sporco o deformato Elettr...

Page 23: ...e simulation Hydraulic circuit not pressurising with consequent lock out at ignition Valve 12 Fig 4 not closing coil interrupted pre heating element not operat ing Lock out at ignition Dirty or missha...

Page 24: ...R B L Riello Bruciatori Legnago s p a Via degli Alpini 1 I 37045 Legnago VR Tel 442 630111 Fax 442 21980 Con riserva di modi che Subject modi cations...

Reviews: