2146
6
GB
3.4
GAS TRAIN,
(as EN 676)
The gas train is supplied separately, for its adjustment see the enclosed instructions.
3.5
GAS TRAIN ELECTRICITY SUPPLY
The gas train’s power cables can be fed to the right or
left of the burner, as illustrated in figure 6.
Depending on the entry point, the cable clamp with
pressure test point (1) and simple cable clamp (2) may
need swapping over.
Consequently, you must make sure:
➤
cable clamp (1) is positioned correctly;
➤
the tube is positioned correctly so that there are no
restrictions likely to impede air flowing to the pres-
sure switch.
WARNING
If necessary, cut the tube to the right size.
3.6
GAS FEEDING LINE
GAS TRAIN
MATCHED
BURNER
CONNECTIONS
USE
TYPE
CODE
INLET
OUTLET
MB DLE 055 D01
3970562
BS1
Rp 1/2
Flange 1
Natural gas and LPG
MB DLE 403 B01
3970085
BS1
Rp 1/2
Flange 1
Natural gas
≤
40/45kW and LPG
MB DLE 405 B01
3970086
BS1
Rp 1/2
Flange 1
Natural gas and LPG
MB DLE 405 B01
3970087
BS2
Rp 3/4
Flange 2
Natural gas and LPG
MB DLE 407 B01
3970069
BS2
Rp 3/4
Flange 2
Natural gas and LPG
MB DLE 407 B01
3970088
BS3 - BS4
Rp 3/4
Flange 3
Natural gas
≤
150kW and LPG
MB DLE 410 B01
3970092
BS3 - BS4
Rp 1 1/4
Flange 3
Natural gas and LPG
MB DLE 412 B01
3970093
BS3 - BS4
Rp 1 1/4
Flange 3
Natural gas
2
1
2
D4605
1
Fig. 6
1
– Gas supply pipe
2
– Manual cock
(charged to the installer)
3
– Gas pressure gauge
(charged to the installer)
4 – Filter
5
– Gas pressure switch
6 – Safety
valve
7 – Pressure
governor
8 – Adjusting
valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
M2
Fig. 7
D5209
1
2
3
M1
5
6
7
4
8