6.

FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner. A fault usually makes the lock-out lamp light which is situated
inside the reset button of the control box (9, fig. 1, page 1). 
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found.

BURNER STARTING DIFFICULTIES 

 

Signal

Problem

Possible cause

Recommended remedy

2 blinks

Once the pre-purging 
phase and safety time 
have passed, the 
burner goes into lock-
out without the appear-
ance of the flame

1

- The operation solenoid lets little . . . . . . . .

gas through

Increase

2

- One of the two solenoid valves does  . . . .

not open.

Replace

3

- Gas pressure too low  . . . . . . . . . . . . . . . . Increase pressure at governor

4

- Ignition electrode incorrectly adjusted . . . . Adjust, see page 4

5

- Electrode grounded due to broken  . . . . . .

insulation

Replace

6

- High voltage cable defective . . . . . . . . . . . Replace

7

- High voltage cable deformed by high  . . . .

temperature

Replace and protect

8

- Ignition transformer defective  . . . . . . . . . . Replace

9

- Incorrect valve or transformer   . . . . . . . . .

electrical wiring

Check

10 - Defective control box. . . . . . . . . . . . . . . . . Replace
11 - A closed valve upline the gas train . . . . . . Open
12 - Air in pipework. . . . . . . . . . . . . . . . . . . . . . Bleed air

13 - Gas valves unconnected or with   . . . . . . .

interrupted coil

Check connections or replace coil

3 blinks

The burner does not 
switch on, and the 
lockout appears

14 - Air pressure switch in operating position. . Adjust or replace

The burner switches 
on, but then stops in 
lockout

-  Air pressure switch inoperative due to 

insufficient air pressure:

15 - Air pressure switch incorrectly adjusted. . . Adjust or replace
16 - Pressure switch pressure test point  . . . . .

pipe blocked

Clean

17 - Poorly adjusted head  . . . . . . . . . . . . . . . . Adjust

18 - High pressure in the furnace . . . . . . . . . . . Connect air pressure switch to fan 

suction line

Lockout during pre-
purging phase

19 - Defective motor control contactor . . . . . . .

(only three-phase version)

Replace

20 - Defective electrical motor  . . . . . . . . . . . . . Replace

21 - Motor lockout (defective electrical motor) . Replace

4 pulses

The burner switches 
on, but then stops in 
lockout

22 - Flame simulation . . . . . . . . . . . . . . . . . . . . Replace the control box

Lockout when burner 
stops

23 - Permanent flame in the combustion . . . . .

head or flame simulation

Eliminate persistence of flame or 
replace control box

7 blinks

The burner goes into 
lockout immediately 
following the appear-
ance of the flame

24 - The operation solenoid lets little . . . . . . . .

gas through

Increase

25 - Ionisation probe incorrectly adjusted. . . . . Adjust, see page 4
26 - Insufficient ionisation (less than 5 A). . . . . Check probe position

27 - Earth probe . . . . . . . . . . . . . . . . . . . . . . . . Withdraw or replace cable
28 - Burner poorly grounded  . . . . . . . . . . . . . . Check grounding
29 - Phase and neutral connections inverted . . Invert them

30 - Defective flame detection circuit . . . . . . . . Replace the control box

Burner goes into lock-
out during operation

31 - Probe or ionisation cable grounded  . . . . . Replace worn parts

Summary of Contents for 40 GS20

Page 1: ...nto Installatie gebruiks en onderhoudsvoorschriften Gas Gebl sebrenner Br leur gaz air souffl Forced draught gas burner Gasventilatorbrander Quemador de gas de aire soplado CODE C DIGO MODELL MODELE M...

Page 2: ......

Page 3: ...7 4 5 Air pressure switch 7 4 6 Burner start up cycle 8 4 7 Start up cycle diagnostics 8 4 8 Resetting the control box and using diagnostics 9 5 MAINTENANCE 10 6 FAULTS SOLUTIONS 11 1 Air damper actua...

Page 4: ...A Secondary 8 kV 30 mA Absorbed electrical power 0 25 kW 1 Reference conditions Temp 20 C Barometric pressure 1013 mbar Altitude 0 m above sea level COUNTRY AT DE ES GB IE LU NL GAS CATEGORY II2H3B P...

Page 5: ...th the combustion chamber at 0 mbar using gas G20 with a net heat value of 10 kWh Nm3 8 570 kcal Nm3 3 INSTALLATION THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS 3 1...

Page 6: ...3 4 Natural gas 80 kW and LPG MBDLE 410 B01 3970532 Rp 1 Rp 3 4 Natural gas and LPG D5104 Ignition electrode WARNING 2 3 mm Ionization probe Probe Electrode 3 7 47 mm Diffuser 1 Gas supply pipe 2 Manu...

Page 7: ...30V 50Hz D4198 switch ATTENTION Do not swap neutral and phase over follow the diagram shown carefully and carry out a good earth connection The section of the conductors must be at least 1mm Unless re...

Page 8: ...e of the coupling C coincides with the set point Tighten the screw A Example The burner is installed on a 155 kW boiler with an efficiency of 90 the burner input is about 172 kW using the diagram the...

Page 9: ...TCH The air pressure switch is set after all other adjustments have been made Begin with the switch at the low est setting With the burner working at the minimum output adjust the dial clockwise incre...

Page 10: ...n is according to the followin table COLOUR CODE TABLE Sequences Colour code Pre purging Ignition phase Operation flame ok Operating with weak flame signal Electrical supply lower than 170V Lock out E...

Page 11: ...ght pulses to tell you the operation is done Release the button once the light pulses The number of times it pulses tells you the cause of the mal function indicated in the table below SOFTWARE DIAGNO...

Page 12: ...nual Then carry out a combustion check verifying CO2 content Smoke temperature at the chimney CO content ppm SIGNAL PROBABLE CAUSE 2 pulses The flame does not stabilise at the end of the safety time f...

Page 13: ...Bleed air 13 Gas valves unconnected or with interrupted coil Check connections or replace coil 3 blinks The burner does not switch on and the lockout appears 14 Air pressure switch in operating posit...