N.B.: 

If problems still occur after all of the above checks have been made, check the electrical connec-
tions on the plug and sockets, the damper and burner motor, gas control wiring ignition transformer
and external interlocks, if the burner still fails to function, replace the control box.

10 blinks

The burner does not 
switch on, and the 
lockout appears

32 - Incorrect electrical wiring . . . . . . . . . . . . .  Check

The burner goes into 
lockout

33 - Defective control box . . . . . . . . . . . . . . . .  Replace
34 - Presence of electromagnetic . . . . . . . . . . 

disturbances inthe thermostat lines

Filter or eliminate 

No blink

The burner does not 
start 

35 - No electrical power supply . . . . . . . . . . . .  Close all switches - Check connec-

tions

36 - A limiter or safety control device is open .  Adjust or replace
37 - Line fuse blocked . . . . . . . . . . . . . . . . . . .  Replace

38 - Defective control box . . . . . . . . . . . . . . . .  Replace
39 - No gas supply. . . . . . . . . . . . . . . . . . . . . .  Open the manual valves between 

contactor and train

40 - Mains gas pressure insufficient  . . . . . . . .  Contact your GAS COMPANY

41 - Minimum gas pressure switch fails  . . . . . 

to close

Adjust or replace

42 - Servomotor fails to move to min. . . . . . . . 

ignition position

Replace

The burner continues 
to repeat the start-up 
cycle, without lockout

43 - The gas pressure in the gas mains lies 

very close to the value to which the mini-
mum gas pressure switch has been set. 
The sudden drop in pressure after valve 
opening causes temporary opening of the 
pressure switch itself, the valve immedi-
ately closes and the burner comes to a 
halt. Pressure increases again, the pres-
sure switch closes again and the ignition 
cycle is repeated. And so on

Reduce the minimum gas pressure 
switch intervention pressure. 
Replace the gas filter cartridge.

Ignition with pulsations 44 - Poorly adjusted head . . . . . . . . . . . . . . . .  Adjust. See page 6

45 - Ignition electrode incorrectly adjusted  . . .  Adjust, see page 4
46 - Incorrectly adjusted fan air damper:   . . . . 

too much air

Adjust

47 - Output during ignition phase is too high . .  Reduce

Burner stops with air 
damper open

48 - Defective servomotor . . . . . . . . . . . . . . . .  Replace

Signal

Problem

Possible cause

Recommended remedy

Summary of Contents for 40 GS20

Page 1: ...nto Installatie gebruiks en onderhoudsvoorschriften Gas Gebl sebrenner Br leur gaz air souffl Forced draught gas burner Gasventilatorbrander Quemador de gas de aire soplado CODE C DIGO MODELL MODELE M...

Page 2: ......

Page 3: ...7 4 5 Air pressure switch 7 4 6 Burner start up cycle 8 4 7 Start up cycle diagnostics 8 4 8 Resetting the control box and using diagnostics 9 5 MAINTENANCE 10 6 FAULTS SOLUTIONS 11 1 Air damper actua...

Page 4: ...A Secondary 8 kV 30 mA Absorbed electrical power 0 25 kW 1 Reference conditions Temp 20 C Barometric pressure 1013 mbar Altitude 0 m above sea level COUNTRY AT DE ES GB IE LU NL GAS CATEGORY II2H3B P...

Page 5: ...th the combustion chamber at 0 mbar using gas G20 with a net heat value of 10 kWh Nm3 8 570 kcal Nm3 3 INSTALLATION THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS 3 1...

Page 6: ...3 4 Natural gas 80 kW and LPG MBDLE 410 B01 3970532 Rp 1 Rp 3 4 Natural gas and LPG D5104 Ignition electrode WARNING 2 3 mm Ionization probe Probe Electrode 3 7 47 mm Diffuser 1 Gas supply pipe 2 Manu...

Page 7: ...30V 50Hz D4198 switch ATTENTION Do not swap neutral and phase over follow the diagram shown carefully and carry out a good earth connection The section of the conductors must be at least 1mm Unless re...

Page 8: ...e of the coupling C coincides with the set point Tighten the screw A Example The burner is installed on a 155 kW boiler with an efficiency of 90 the burner input is about 172 kW using the diagram the...

Page 9: ...TCH The air pressure switch is set after all other adjustments have been made Begin with the switch at the low est setting With the burner working at the minimum output adjust the dial clockwise incre...

Page 10: ...n is according to the followin table COLOUR CODE TABLE Sequences Colour code Pre purging Ignition phase Operation flame ok Operating with weak flame signal Electrical supply lower than 170V Lock out E...

Page 11: ...ght pulses to tell you the operation is done Release the button once the light pulses The number of times it pulses tells you the cause of the mal function indicated in the table below SOFTWARE DIAGNO...

Page 12: ...nual Then carry out a combustion check verifying CO2 content Smoke temperature at the chimney CO content ppm SIGNAL PROBABLE CAUSE 2 pulses The flame does not stabilise at the end of the safety time f...

Page 13: ...Bleed air 13 Gas valves unconnected or with interrupted coil Check connections or replace coil 3 blinks The burner does not switch on and the lockout appears 14 Air pressure switch in operating posit...

Page 14: ...insufficient Contact your GAS COMPANY 41 Minimum gas pressure switch fails to close Adjust or replace 42 Servomotor fails to move to min ignition position Replace The burner continues to repeat the st...

Page 15: ...approximately 3 seconds The number of pulses will measure the probe DETECTION TIME since the opening of gas valves according to the following table KIT INTERFACE ADAPTER RMG TO PC Code 3002719 SIGNAL...

Page 16: ...I 37045 Legnago VR Tel 39 0442 630111 http www rielloburners com nderungen vorbehalten Sous r serve de modifications Subject to modifications Onder voorbehoud van wijzigingen Con la posibilidad de mo...

Reviews: